Installing Front/Side External Supply Plenums; Using The Uni-Strut; Using Hanger Brackets And Threaded Rod; Installing The Supply Duct Collar To The Plenum - Accurex XB Installation, Operation And Maintenance Manual

Kitchen hoods type i and type ii
Table of Contents

Advertisement

Installing Front/Side External Supply Plenums

Using the Uni-strut

THREADED ROD
SUPPLIED BY OTHERS
UNI-STRUT (U-CHANNEL)
SUPPLIED BY OTHERS
END VIEW
HOOD
The uni-strut (supplied by others) supporting the hood
may be cantilevered over the end of the hood. Utilizing
the external supply plenum's hanger brackets, securely
fasten to the uni-strut.
THREADED
THREADED
ROD
ROD
UNI-STRUT
UNI-STRUT
(U-CHANNEL)
(U-CHANNEL)
Air Curtain Supply (ASP)
Horizontal Supply Plenum (HSP)
Variable Supply Plenum (VSP)
Mounted with uni-strut and threaded rod
When using the uni-strut (supplied by others), it must be
bolted to the hood and external supply plenum hanger
brackets.
NOTE
The uni-strut needs to be the full length of the hood
and the external supply plenum.

Using Hanger Brackets and Threaded Rod

Air Curtain
Supply Plenum (ASP)
10
Kitchen Hoods • Type I and Type II
EXTERNAL
SUPPLY
PLENUM
Horizontal Supply Plenum (HSP)
Variable Supply Plenum (VSP)
1. Insert 1/2 in. (12.7 mm) diameter threaded rod (by
others) into hanger brackets on the external supply
plenum top. Raise and hang the external supply
plenum from adequate roof or ceiling supports.
NOTE
Ensure the external supply plenum is installed
flush with the hood front and is plumb and level by
adjusting the threaded rod(s). There should be no gap
between the bottom of the external supply plenum
and the hood after installation and adjustments are
completed.
2. The external supply plenum should be resting
lightly against the hood. The hood is only used to
position the plenum; it is not intended to support the
plenum. All hanger brackets on the external supply
plenum must be used and the plenum must be
properly supported while lifting to prevent damage or
distortion. The external supply plenum must be level
to operate properly.
NOTE
After hanging, secure the external supply plenum to
the hood (or to another external supply plenum) using
the supplied turnbuckle(s). Use caution tensioning the
turnbuckle. Too much tension may cause the bottom
of the external supply plenum to pull away from
the hood or cause the face of the hood to become
deformed.
TURNBUCKLE
TURNBUCKLE
EXTERNAL
EXTERNAL
SUPPLY PLENUM
SUPPLY PLENUM
HANGER BRACKET
HANGER BRACKET
3. It is recommended that caulk be applied at the
mating seams and surfaces of the external supply
plenum, the hood, and the wall. If the external supply
plenum is next to a wall, you will need to caulk
around the surface next to the wall. Caulk the joints
with NSF Approved silicone caulk (GE SCS1009, or
its equivalent). The caulk is not provided.

Installing the Supply Duct Collar to the Plenum

Place the duct collar(s) over the opening, fastening
with tack-welds at 1 to 2 in. (2.54 to 5.08 cm) intervals,
or sheet metal screws at 3 to 6 in. (7.62 to 15.24 cm)
intervals.
HOOD HANGER
HOOD HANGER
BRACKET
BRACKET
HOOD
EXTERNAL
SUPPLY
PLENUM