Wireless Smoke Detector
,1752'8&7,21
The WST-400 consists of a 9-Volt battery-operated smoke
detector to which a Visonic Ltd. RF transmitter has been added.
The transmitter is compatible with the Visonic Ltd. 1, 2, and 4
channel receivers of the WR-200 and WR-300 series.
Upon alarm (smoke detection), the detector keys the RF
transmitter. The transmitter in turn transmits a coded signal that
consists of a SYSTEM code and a CHANNEL code. Only a
receiver set to the same system code as that of the transmitter
will respond to the transmitted signal. If the system code is
correct, the channel code transmitted by the WST-400 will
activate the corresponding relay in the target receiver.
Smoke alarm transmissions will be sent once every 60 seconds
for a period of 1 - 2 seconds per transmission while the detector
is on alarm. An alarm is also indicated by sounding of the smoke
detector's built-in horn.
A notable advantage of the WST-400 is its ability to transmit
low-battery signals when the battery voltage drops below a preset
75$160,77(563(&,),&$7,216
Encoding: 8-bit digital word, 256 combinations, pulse width
modulation.
Channels: 4 channels, DIP switch selectable
Operating Frequency (MHz): 315, 404, 418, 433.92 MHz or
other frequencies according to local requirements.
Transmission Cycle: 1-2 second transmissions once every 60
seconds while in alarm.
Power Supply: 9 VDC alkaline battery, such as Eveready #522
or Duracell #MN1604
,167$//$7,21
6HWWLQJWKH6\VWHP&RGH
The WST-400 transmitter has an 8-key DIP switch marked 1 to 8
(see Figure 1). Each key may be set to ON or OFF to create a
unique digital code (256 possible combinations). Use a ball point
pen to set each one of the 8 switches to match the system code
setting of the target receiver. All wireless transmitters and
receivers in the system must be set to the same code.
Figure 1. WST-400 Code Selector
CAUTION! The code combination 2, 4, 5, 6, 7 ON / 1, 3, 8 OFF
is a factory test code which must not be used. Also avoid codes
which are often used: all keys ON, all keys OFF or alternating
ON/OFF settings.
6HWWLQJWKH&KDQQHO&RGH
Each WST-400 has a 4-key DIP switch marked 1 to 4 (Fig. 1).
This switch permits selecting one of 4 channel codes by shifting
DE3541

Installation Instructions

threshold. A low battery signal will be sent once every 45
seconds for 1 to 2 seconds per transmission, to activate the
buzzer output (BUZ) in receivers type WR-200/2B, WR-200/4B,
WR-300/2B
and
WR-300/4B.
electronic horn will sound a short beep.
Current Consumption: 0.5 µA standby, 5 mA transmit
Battery Test: "Channel 0" code transmitted once every 45
seconds when the battery voltage goes below 7.5 Volts.
Compliance with Standards: Meets FCC Part 15, ETS300-220
and MPT1349
Operating Temperature Range: 0°C to 49°C (32°F to 120°F).
the selected switch lever to the ON position. Figure 1 shows the
channel selector with channel No. 2 selected.
Setting all four channel selector keys to OFF (code "0") will
activate the buzzer (BUZ) output in the receiver and none of the
channel outputs.
In fact, the channel selector keys can be set to 15 ON/OFF
combinations - a useful feature in multiple zone applications. To
take advantage of this capability, the 4 outputs of the target
receiver must be connected to the optional WMX-16 output
multiplexer (refer to Publication D-4001-0 for more details).
0RXQWLQJ
Mount the WST-400 smoke detector in accordance with the
enclosed owner's manual. Be sure to read these instructions and
follow them in full.
7HVWLQJ
ATTENTION! Before proceeding, be sure to put the alarm
system into the test mode, or inform the central station that you
will be testing your smoke detectors.
To test proper activation of the smoke detector as well as
wireless transmission, press the test button located on the front
of the smoke detector for 20 seconds or until the alarm sounds.
Verify activation of the control panel's fire zone (the zone
designated for smoke detectors).
See the enclosed owner's manual for more information.
Simultaneously,
the
built-in
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the WST-400 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Visonic WST-400

  • Page 1: Installation Instructions

    Verify activation of the control panel's fire zone (the zone 6HWWLQJWKH&KDQQHO&RGH designated for smoke detectors). See the enclosed owner's manual for more information. Each WST-400 has a 4-key DIP switch marked 1 to 4 (Fig. 1). This switch permits selecting one of 4 channel codes by shifting DE3541...
  • Page 2 VISONIC INC. (U.S.A.): 10 NORTHWOOD DRIVE, BLOOMFIELD CT. 06002-1911. PHONE: (860) 243-0833, (800) 223-0020 FAX: (860) 242-8094 VISONIC LTD. (UK): UNIT 1, STRATTON PARK, DUNTON LANE, BIGGLESWADE, BEDS. SG18 8QS. PHONE: (01767) 600857 FAX: (01767) 601098 ©VISONIC LTD. 1998 WST-400 D-3541-0 NEW : DE3541- (REV. 3 , 4/98)

Table of Contents