Mitsubishi Electric MXZ-8A140VA Technical & Service Manual page 78

Split-type, heat pump air conditioners
Hide thumbs Also See for MXZ-8A140VA:
Table of Contents

Advertisement

SW2 setting
Target Sub-cool (Cooling mode) : SCm
ON
1
2 3 4 5 6
Error postponement code history (2)
of outdoor unit
ON
1
2 3 4 5 6
Error postponement code history (3)
of outdoor unit
ON
1
2 3 4 5 6
Error code history (3) (Oldest)
ON
Alternate display of abnormal unit num-
ber and code
1
2 3 4 5 6
Error thermistor display
ON
When there is no error thermistor,
"–" is displayed.
1
2 3 4 5 6
Operation frequency on error occurring
0~255
ON
1
2 3 4 5 6
Fan step on error occurring
0~10
ON
1
2 3 4 5 6
LEV opening pulse on error occurring
0~500
ON
1
2 3 4 5 6
Indoor room temperature
on error occurring
8~39
ON
1
2 3 4 5 6
Display detail
SW1
4
5
6
Indoor unit 1
0
0
0
Indoor unit 2
1
0
0
Indoor unit 3
0
1
0
Indoor unit 4
1
1
0
Indoor unit 5
0
0
1
Indoor unit 6
1
0
1
Indoor unit 7
0
1
1
Indoor unit 8
1
1
1
SW1
4
5
6
Indoor unit 1
0
0
0
Indoor unit 2
1
0
0
Indoor unit 3
0
1
0
Indoor unit 4
1
1
0
Indoor unit 5
0
0
1
Indoor unit 6
1
0
1
Indoor unit 7
0
1
1
Indoor unit 8
1
1
1
Explanation for display
0~255
Postponement code display
Blinking: During postponement
Lighting: Cancellation of postponement
"00" is displayed in case of no postponement.
Postponement code display
Blinking: During postponement
Lighting: Cancellation of postponement
"00" is displayed in case of no postponement.
When no error history, "0" and "–" are displayed by
turns.
3
: Outdoor pipe temperature /Liquid (TH3)
7
: Outdoor outside temperature (TH7)
8
: Outdoor radiator panel (TH8)
23
: Branch box pipe temperature / Gas (TH–A~E)
63
: High pressure sensor (63HS)
0~255
(When it is 100Hz or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
(Example)
When 125Hz; 0.5 secs.
0.5secs.
1
0~10
0~500
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example)
When 130 pulse; 0.5 secs.
1
8~39
78
2 secs.
25
0.5secs.
2 secs.
30
Unit
:
Code
display
Code
display
Code
display
Code
display
Hz
Step
Pulse
:

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents