Mitsubishi Electric MXZ-8A140VA Technical & Service Manual page 56

Split-type, heat pump air conditioners
Hide thumbs Also See for MXZ-8A140VA:
Table of Contents

Advertisement

BRANCH BOX : PAC-AK50BC
PAC-AK30BC
Parts name
Disconnect the connector then measure the resistance with a tester.
Thermistor (TH-A~E)
(At the ambient temperature 10:~30:)
<Gas pipe>
Disconnect the connector then measure the resistance with a tester.
Linear expansion valve
(Winding temperature 20:)
( LEV-A~E )
Red
Red - White Red - Orange Brown - Yellow Brown - Blue
M
1
Brown
2
Blue
3
Orange
4
Yellow
5
White
6
Normal
4.3k"~9.6k"
Normal
46±4"
Check points
Abnormal
Open or short
Abnormal
Open or short
56