Physical And Electrical Specifications - IBM System x3250 M5 Product Manual

Single-socket 1u rack server
Table of Contents

Advertisement

Physical and electrical specifications

Dimensions and weight (approximate):
Height: 43 mm (1.7 in.)
Width: 435 mm (17.1 in.)
Depth: 576 mm (22.7 in.)
Maximum weight: 12.3 kg (27.1 lb).
Shipping dimensions and weight (approximate):
Height: 230 mm (9.1 in.)
Width: 590 mm (23.2 in.)
Depth: 1000 mm (39.4 in.)
Weight (single pack): 12.9 kg (28.4 lb).
Supported environment:
Air temperature:
Server on: 10 °C - 35 °C (50 °F - 95 °F); altitude: 0 - 914 m (3,000 ft).
Server on: 10 °C - 32 °C (50 °F - 89.6 °F); altitude: 914 - 2,134 m (7,000 ft).
Server off: 10 °C - 43 °C (50 °F - 109.4 °F).
Shipment: -40 °C - 60 °C (-40 °F - 140 °F).
Humidity: 8% - 80%
Electrical:
Models with 460 W redundant hot-swap power supplies:
100 - 127 (nominal) V AC; 50 Hz or 60 Hz; 5.3 A
200 - 240 (nominal) V AC; 50 Hz or 60 Hz; 2.6 A
Models with 300 W hot-swap power supplies:
100 - 127 (nominal) V AC; 50 Hz or 60 Hz; 6.0 A
200 - 240 (nominal) V AC; 50 Hz or 60 Hz; 3.0 A
Input kilovolt-amperes (kVA) (approximately):
Minimum configuration: 0.04 kVA
Maximum configuration: 0.50 kVA
BTU output:
Ship configuration: 130 Btu/hr (38 watts)
Full configuration: 1720 Btu/hr (504 watts)
Noise level:
6.5 bels (operating)
6.5 bels (idle)