Drain Exiting Left Side - Goodman xMEC96 Series User Manual

Upflow / horizontal two-stage gas furnace
Table of Contents

Advertisement

D
E
L
S
RAIN
XITING
EFT
IDE
1. Install the 45 degree pipe / hose drain coupling from the outside of the cabinet (barbed end goes in the cabinet)
through the hole in the left side of the cabinet and secure with two field supplied #8 self-tapping screws (see Figure
21).
2. Locate the long drain hose #3 and cut at "B" line for a 17.5" cabinet; cut at line "C" for a 21" cabinet; do not cut for
a "D" width cabinet.
3. Install large end of hose #3 to trap outlet and secure with 1.25" clamp.
4. Install smaller end of hose #3 on 45º elbow and secure with 1" clamp.
5. Refer to Field Supplied Drain section for instructions on field supplied / installed drain on outlet of furnace trap.
U
M
I
PFLOW
ODEL
NSTALLED
D
OWN
Minimum 5 1/2" clearance is required for the drain trap be-
neath the furnace.
1. Remove the clamps from both ends of the drain hoses.
2. Remove the two screws holding the drain trap to the blower
deck.
3. Remove the trap and two hoses from the blower deck
4. Remove the two plugs from the right side of the cabinet
and install them in the blower deck.
5. (Draining the Vent Elbow ) Locate hose #5 and cut it at line
"C". Install the cut end of hose #5 from outside the cabinet
through the cabinet drain hole nearest the top. Secure it
to the barbed fitting in the elbow with a red clamp.
6. (Draining the Collector Box) Install the non-grommet end
of hose #11 from outside the cabinet in the bottom drain
hole. Install on collector box and secure with a silver clamp.
7. Use two silver clamps and secure the hoses to drain trap. The trap outlet faces the front of the furnace. Secure the
trap to the cabinet using two screws removed in step 2 by inserting the two screws through the large set of holes in the
top mounting tabs of the trap into the two predrilled holes in the side of the cabinet.
8. Refer to Field Supplied Drain section for instructions on field supplied / installed drain on outlet of furnace trap.
U
M
I
PFLOW
ODEL
NSTALLED
D
OWN
Minimum 5 1/2" clearance is required for the drain trap be-
neath the furnace.
*Also see Front Cover Pressure Switch Tube Location on page
10.
1. Remove the clamps from the two drain tubes on the trap.
2. Remove the two screws holding the drain trap to the blower
deck.
3. Remove the trap and hoses from the blower deck .
4. Remove the two plugs from the left side of the cabinet
and install them in the blower deck.
5. (Draining the Vent Elbow) Locate hose #6. Measuring from
the non-grommet end; cut off and discard 1 ½" for a "D"
width cabinet, 5" for a "C" width cabinet, 8 ½" for a "B"
width cabinet.
6. Remove the rubber plug from vent – drain elbow side port.
Place hose #6 on the vent – drain elbow side port and secure with a silver clamp .
7. Place cap on vent – drain elbow barb fitting and secure with red clamp
8. Locate hose #5 and cut 3" from the non-grommet end. Discard the section without the grommet.
9. Insert the cut end of tube #5 through the lower cabinet drain hole.
H
R
ORIZONTALLY WITH
IGHT
H
L
ORIZONTALLY WITH
EFT
S
IDE
S
IDE
Hose #6
Hose #5
20
Hose #5-Cut at "C"
Hose #11
Figure 22
Hose #11
Figure 23