Fossil Fuel Applications; F F A; 115 Volt Line Connection Of Accessories (Humidifier And Electronic Air Cleaner ); Volt Humidifier - Goodman GMV95 Installation Instructions Manual

Two-stage gas-fired warm air furnace
Table of Contents

Advertisement

tioned air as it passes through the AC coil. For proper function, a
dehumidistat applied to this furnace must operate on 24 VAC and
utilize a switch which opens on humidity rise.
To install/connect a dehumidistat:
1. Turn OFF power to furnace.
2. Secure the dehumidistat neutral wire (typically the white lead)
to the screw terminal marked "DEHUM" on the furnace
integrated control module.
3. Secure the dehumidistat hot wire (typically the black lead) to
the screw terminal marked "R" on the furnace integrated
control module.
4. Secure the dehumidistat ground wire (typically the green lead)
to the ground screw on the furnace junction box. NOTE:
Ground wire may not be present on all dehumidistats.
5. Turn ON power to furnace.
To enable the dehumidify function on the integrated control module:
1. Cut the jumper wire labeled "CUT FOR DEHUM" located
adjacent to the DEHUM screw terminal.
Once the jumper wire is cut, the dehumidify function is enabled dur-
ing a combination call for cooling (T-Stat) and dehumidification
(Dehum-Stat). The yellow LED adjacent to the DEHUM screw ter-
minal will be illuminated during dehumidification.
0
YL0
Y
B/C
G
0
YL0
Y
B/C
G
F
F
A
OSSIL
UEL
PPLICATIONS
This furnace can be used in conjunction with a heat pump in a fossil
fuel application. A fossil fuel application refers to a combined gas
furnace and heat pump installation which uses an outdoor tempera-
ture sensor to determine the most cost efficient means of heating
(heat pump, gas furnace, or both).
A heat pump thermostat with three stages of heat is required
to properly use a two-stage furnace in conjunction with a heat
pump. Refer to the fossil fuel kit installation instructions for
additional thermostat requirements.
Strictly follow the wiring guidelines in the fossil fuel kit instal-
lation instructions. All furnace connections must be made to
the furnace two-stage integrated control module and the
"FURNACE" terminal strip on the fossil fuel control board.
115 V
L
C
OLT
INE
ONNECTION OF
E
A
C
AND
LECTRONIC
IR
LEANER
T
O AVOID INJURY, ELECTRICAL SHOCK OR DEATH, DISCONNECT ELECTRICAL
POWER BEFORE SERVICING OR CHANGING ANY ELECTRICAL WIRING.
The furnace's integrated control module is equipped with line volt-
age accessory terminals for controlling power to an optional field-
supplied humidifier and/or electronic air cleaner.
The accessory load specifications are as follows:
Humidifier
Electronic Air Cleaner
Turn OFF power to the furnace before installing any accessories.
Follow the humidifier or air cleaner manufacturers' instructions for
locating, mounting, grounding, and controlling these accessories.
DEHUM
R
W1 W2
TWIN
DEHUMIDIFICATION
LED (YELLOW)
R
W1 W2
CUT FOR
DEHUMIDIFICATION
DEHUM
JUMPER WIRE
(CUT TO ENABLE)
A
(H
CCESSORIES
UMIDIFIER
)
WARNING
1.0 Amp maximum at 120 VAC
1.0 Amp maximum at 120 VAC
Accessory wiring connections are to be made through the 1/4"
quick connect terminals provided on the furnace integrated control
module. The humidifier and electronic air cleaner hot and neutral
terminals are identified as HUM and EAC. All field wiring must
conform to applicable codes. Connections should be made as
shown.
CONTROL MODULE
CONTROL MODULE
OPTIONAL ACCESSORIES
OPTIONAL ACCESSORIES
Accessories Wiring
If it is necessary for the installer to supply additional line voltage
wiring to the inside of the furnace, the wiring must conform to all
local codes, and have a minimum temperature rating of 105°C. All
line voltage wire splices must be made inside the furnace junction
box.
The integrated control module humidifier terminals (HUM) are ener-
gized with 115 volts whenever the induced draft blower is energized.
The integrated control module electronic air cleaner terminals (EAC)
are energized with 115 volts whenever the circulator blower is ener-
gized.
24 V
H
OLT
UMIDIFIER
A 5" long brown wire in the wire harness at the low fire pressure
provides 24 VAC humidifier control. This wire is powered any time
the pressure switch is closed. To connect 24 VAC HUM, connect
the 24 VAC line of the humidifier to the 5" brown wire. The connec-
tion can be made by either stripping the wire and using a wire nut or
by using a field supplied quick connect terminal. The wiring must
conform to all local and national codes. Connect the COM side of
the humidifier to the B/C terminal on the furnace control board (or to
the COM side of the 24 VAC transformer). Do not connect 115V
humidifier to these terminals.
XII. GAS SUPPLY AND PIPING
G
ENERAL
The furnace rating plate includes the approved furnace gas input
rating and gas types. The furnace must be equipped to operate on
the type of gas applied. This includes any conversion kits required
for alternate fuels and/or high altitude.
T
O PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE, THE INLET
GAS SUPPLY PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE
WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES OPERATING.
Inlet gas supply pressures must be maintained within the ranges
specified below. The supply pressure must be constant and avail-
able with all other household gas fired appliances operating. The
minimum gas supply pressure must be maintained to prevent unre-
liable ignition. The maximum must not be exceeded to prevent unit
overfiring.
23
12 CIRCUIT
12 CIRCUIT
CONNECTOR
CONNECTOR
INTEGRATED
INTEGRATED
HUMIDIFIER
HUMIDIFIER
ELECTRONIC
ELECTRONIC
AIR CLEANER
AIR CLEANER
CAUTION

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gcv9

Table of Contents