Specifications And Electrical Data - Lennox T?CLASS TPA024S4 Unit Information

T?class tpa*s4 m and t voltage units
Table of Contents

Advertisement

Specifications and Electrical Data1

SPECIFICATIONS − SINGLE PHASE
General
Data
Connections
(sweat)
1
Refrigerant (R−410A) furnished
Net face area
Outdoor
2
Coil
m
(sq. ft.)
Outdoor
Fan
Shipping Data − kg (lbs.) 1 package
Electrical Data
2
Maximum overcurrent protection (amps)
Compressor
Outdoor
Fan Motor
NOTE − Extremes of operating range are plus 10% and minus 5% of line voltage.
1
Refrigerant charge sufficient for 4.6 m (15 ft.) length of refrigerant lines.
2
Heating Air Conditioning and Refrigeration type circuit breaker or fuse.
3
Refer to local codes to determine wire, fuse and disconnect size requirements.
Model No.
Nominal kW
Liquid line o.d. − in.
Vapor line o.d. − in.
Outer coil
Inner coil
Tube diameter − in.
Number of rows
Fins per meter (inch)
Diameter − mm (in.)
Number of blades
Motor W (hp)
L/s (Cfm)
Rev / min
Watts
Line voltage data − 50 hz − 1ph
3
Minimum circuit ampacity
Rated load amps
Locked rotor amps
Power factor
Full load amps
Locked rotor amps
TPA024S4
7
3/8
3/4
2.95 kg (6 lbs. 8 oz.)
2.86 kg (6 lbs. 5 oz.)
1.41 (15.21)
− − −
5/16
1
866 (22)
457 (18)
3
149 (1/5)
945 (2000)
942
138
64 (140)
220 / 240V
25
14.7
10.9
60.0
1.1
2.0
1.9
Page 2
TPA036S4
TPA048S4
10.5
3/8
7/8
5.30 kg (11 lbs. 11 oz.)
1.41 (15.21)
1.96 (21.11)
1.44 (15.50)
1.98 (21.31)
5/16
2
866 (22)
866 (22)
457 (18)
559 (22)
4
149 (1/5)
248 (1/3)
965 (2042)
1530 (3242)
917
158
82 (180)
113 (250)
220 / 240V
220 / 240V
35
21.1
16.0
87.0
1.1
2.0
1.9
14.0
3/8
7/8
5/16
2
4
904
313
35
21.6
15.9
98.0
1.7
4.1
4.1