REFRIGERANT SYSTEM DIAGRAM

MXZ-32SV -
E1
MXZ-32SV -
E2
Unit D gas pipe temperature thermistor
Indoor unit
D
Unit C gas pipe temperature thermistor
Indoor unit
C
Unit B gas pipe temperature
thermistor
[12
Indoor unit
B
Unit A gas pipe
temperature thermistor
[12
Indoor unit
A
Capillary tube
[3.0✕[2.0✕ 200
Indoor unit
A
Strainer
Capillary tube
[3.0✕[2.0✕ 200
Indoor unit
B
Strainer
Capillary tube
[3.0✕[2.0✕ 200
Indoor unit
C
Strainer
Capillary tube
[3.0✕[2.0✕ 200
Indoor unit
D
Strainer
Piping length each indoor unit (a, b, c, d)
Total piping length (a+b+c+d)
Height difference between units (H)
Bending point for each unit
Total bending point
❋It does not matter which unit is higher.
G Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes,refer to the
tables below.
G When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe,see 15-1.
Indoor unit
class
Pipe diameter
Liquid
6.35(1/4)
07/09
Gas
9.52(3/8)
Liquid
6.35(1/4)
12(13)
Gas
12.7(1/2)
Liquid
6.35(1/4)
18
Gas
15.88(5/8)
Compressor
High pressure
Discharge
switch 1
temperature
High pressure
thermistor
switch 2
Capillary tube
Oil
separator
[2.5✕ [0.6✕1000
[9.52
Ball valve with
service port
[9.52
Reversing valve
[16
Ball valve with
[6
service port
LEV
[6
LEV
[6
Distributor
LEV
[6
LEV
Extension pipe diameter
Liquid
6.35(1/4)
Gas
9.52(3/8)
Liquid
6.35(1/4)
Gas
12.7(1/2)
Liquid
6.35(1/4)
Gas
15.88(5/8)
[16
Accumulator
[16
Evaporation
temperature
thermistor
(RT67)
Capillary tube
[2.0✕[0.6✕ 750
Defrost
thermistor
[9.52
Strainer
Indoor
units
25m
60m
c
10m
25
60
d
For
Indoor unit A
Indoor unit B
Indoor unit C
Indoor unit D
12
Refrigerant flow in cooling
Refrigerant flow in heating
Reversing valve coil
heating ON
cooling OFF
Strainer
a
b
Outdoor
unit
Unit : mm (inch)
Outdoor unit union diameter
Liquid
Gas
Liquid
Gas
Liquid
Gas
Liquid
Gas
Unit:mm
Outdoor
heat
exchanger
Capillary tube
[4.0✕[2.4✕ 400
Distributor
H
H
H
6.35(1/4)
12.7(1/2)
6.35(1/4)
12.7(1/2)
6.35(1/4)
9.52(3/8)
6.35(1/4)
9.52(3/8)