commissioning)
4 Familiar trouble during commissioning and shooting method

4.1 Indoor trouble diagnose and trouble shooting

trouble
No.
exhibition
indoor
does not
cool, or
1
cooling
effect is
not good
trouble
diagnose
indoor gas
pipe TC1
(three core,
green), liquid
pipe TC2
(three core,
black)sensor
are inserted
conversely,
pushed off or
with wrong
resistance
value
phase
sequence of
EEV
is
converse,
SW08-7
is
ON
evaporator
is
blocked
by
weld or dirt
- 50 -
trouble
shooting
check
sensor
position,
resistanc
e
value(te
mp. 25 ,
TC1/TC2
is 10KΩ)
change
SW08-7 to
OFF
valve action
is
normal
but
no
effect,
collect
the
refrigerant
and charge
nitrogen to
check
and
clean
the
sundries
remark (trouble
diagnose
method)
observe
the
changing
trend
of
indoor
TC1/TC2/EEV
by
dipswitch:
EEV open angle
become
big,
TC1
become
low, open angle
become
small,
TC2
become
high
observe
indoor
TC1/TC2/EEV
by
dipswitch,
after
system
become stable,
EEV
is
displayed open
fully, when
the
unit startup, you
can not hear any
voice
about
refrigerant flow
Part 2