Indoor Unit - Panasonic CS-C12BKPG Service Manual

Multi-split
Hide thumbs Also See for CS-C12BKPG:
Table of Contents

Advertisement

CS-C12BKPG CU-2C24BKP5G / CS-C14BKPG CU-2C23BKP5G / CS-C9BKPG

Indoor Unit

AUTO
OFF / ON
Automatic Operation Button
• Press for < 5s to operate Automatic
operation mode.
(Used when the remote control cannot be used.)
• Press continuously for 5s or < 10s to
operate Test Run/Pump down. "Beep"
sound will be heard at the 5th second.
(Used when test running or servicing.)
• Press continuously for 10s and above to
omit or resume the remote control signal
receiving sound. "Beep, beep" sound will
be heard at the 10th second.
Operation Indication Lamps (LED)
(Green) ........ Lights up in operation,
POWER
(Orange) ........ Lights up in Sleep
SLEEP
(Orange) ....... Lights up in Timer
TIMER
POWERFUL
ECONOMY
Operation Mode
• Cooling, Soft Dry, Air Circulation and
Automatic Mode.
Powerful Operation
• Reaches the desired room temperature
quickly.
Economy Operation
• To reduce electrical power consumption.
blinks in Automatic
Operation Mode
judging.
Mode Operation.
Setting.
(Orange) .. Lights up in Powerful
Mode Operation.
(Green) ..... Lights up in Economy
Mode Operation.
Random Auto Restart Control
• Operation is restarted randomly after
power failure at previous setting mode.
Anti-Freezing Control
• Anti-Freezing control for indoor heat
exchanger. (Cooling and Soft Dry)
Sleep Mode Auto Control
• Indoor Fan operates at Low speed.
• Operation stops after 8 hours.
Indoor Fan Speed Control
• High, Medium and Low.
• Automatic Fan Speed Mode
– Cooling : Fan rotates at Hi, Me and
– Soft Dry: Fan rotates at SLo speed.
Airflow Direction Control
• Automatic air swing and manual adjusted
by remote control for vertical airflow.
• Manually adjusted by hand for horizontal airflow.
Starting Current Control
• Fan motor is delayed for 1.6 seconds
when compressor starts simultaneously.
Time Delay Safety Control
• Restarting is inhibited for appro. 3 minutes.
7 Minutes Time Save Control
• Cooling Operation only.
Anti-Dew Formation Control
• Anti-Dew Formation Control for indoor
unit discharge area.
4
SLo speed. Deodorizing
control is available.
Deodorizing control
is available.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu-2c24bkp5gCu-2c23bkp5gCs-c9bkpgCs-c14bkpg

Table of Contents