Panasonic CU-2C18BKP5G Service Manual

Panasonic CU-2C18BKP5G Service Manual

Multi-split air conditioner
Hide thumbs Also See for CU-2C18BKP5G:

Advertisement

CONTENTS
Multi-Split Air Conditioner
CS-C9BKPG CU-2C14BKP5G
CS-C9BKPG CU-2C18BKP5G
CS-C9BKPG CU-3C20BKP5G
CS-C7BKPG CU-2C19BKP5G
CS-C12BKPG
Page
2
3
6
14
16
18
22
26
34
39
© 2002 Matsushita Air-Conditioning Corp. Sdn. Bhd.
(183914D). All rights reserved. Unauthorized copying
and distribution is a violation of law.
Order No. MAC0201004C8
Page
49
56
60
62
69
70
71
72
73
74

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic CU-2C18BKP5G

  • Page 1: Table Of Contents

    Order No. MAC0201004C8 Multi-Split Air Conditioner CS-C9BKPG CU-2C14BKP5G CS-C9BKPG CU-2C18BKP5G CS-C9BKPG CU-3C20BKP5G CS-C7BKPG CU-2C19BKP5G CS-C12BKPG CONTENTS Page Page 1 Features 11 3-way Valve 2 Functions 12 Servicing Information 3 Product Specifications 13 Troubleshooting Guide 4 Dimensions 14 Technical Data 5 Refrigeration Cycle Diagram...
  • Page 2: Features

    CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 21 Exploded View 24 Replacement Parts List 22 Replacement Parts List 25 Electronic Parts List 26 Electronic Circuit Diagram 23 Exploded View 1 Features • High Efficiency •...
  • Page 3: Functions

    CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 2 Functions Remote Control Self illuminating button OFF / ON I TEMP. Operation OFF / ON Room Temperature Setting Cooling, Soft Dry, Air Circulation Operation. • Temperature Setting (16°C to 30°C)
  • Page 4 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG Indoor Unit AUTO OFF / ON Automatic Operation Button Random Auto Restart Control • Press for < 5s to operate Automatic • Operation is restarted randomly after operation mode.
  • Page 5 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG Outdoor Unit CU-2C14BK, CU-2C18BK, CU-2C19BK & CU-3C20BK Compressor Reverse Rotation Protection Control • To protect compressor from reverse rotation when there is a instantaneous power failure. Overload Protector •...
  • Page 6: Product Specifications

    CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 3 Product Specifications Unit CS-C9BKPG CU-2C14BKP5G Power Source Phase Single Europe: 230 - 220 Oceania: 240 - 220 Cycle Cooling Capacity (1 unit) 2.82 - 2.78 (2 units) 3.62 - 3.58...
  • Page 7 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG Air Circulation Type Cross-flow Fan Propeller Fan Material AS + Glass Fiber 20% AS + Glass Fiber 20% Motor Type Induction (4-poles) Induction (6-poles) Input 29.3 - 26.3 41.75 - 36.80...
  • Page 8 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG Unit CS-C9BKPG CU-2C18BKP5G Power Source Phase Single Europe: 230 - 220 Oceania: 240 - 220 Cycle Cooling Capacity (1 unit) 2.44 - 2.40 (2 units) 4.88 - 4.80...
  • Page 9 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG Air Circulation Type Cross-flow Fan Propeller Fan Material AS + Glass Fiber 20% AS + Glass Fiber 20% Motor Type Induction (4-poles) Induction (6-poles) Input 29.3 - 26.3 117.1 - 103.3...
  • Page 10 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG CS-C9BKPG CU-3C20BKP5G Unit Single Operation Single Operation Double Operation Triple (A, B1, B2) Operation (B1 or B2) (B1 + B2) (A + B1 or B2) (A + B1 + B2)
  • Page 11 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG Type Cross-flow Fan Propeller Fan Circulation Material AS + Glass Fiber AS + Glass Fiber 20% Motor Type Induction (4-poles) Induction (6-poles) Input 29.3 - 26.3 121.82 - 107.91...
  • Page 12 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG One Unit (A) One Unit (B) Unit CS-C12BKPG CS-C7BKPG CU-2C19BKP5G Cooling Capacity (A) 3.55 - 3.52 (B) 2.08 - 2.06 (A+B) 5.63 - 5.58 kcal/h (A) 3,050 - 3,030...
  • Page 13 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG Heat Exchanger Description Evaporator Condenser Tube material Copper Copper Fin material Aluminium Aluminium Fin Type Slit Fin Louver Fin Row / Stage (Plate fin configuration, forced draft) (A) 2 ×...
  • Page 14: Dimensions

    CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 4 Dimensions...
  • Page 15 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG...
  • Page 16: Refrigeration Cycle Diagram

    CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 5 Refrigeration Cycle Diagram...
  • Page 17 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG...
  • Page 18: Block Diagram

    CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 6 Block Diagram...
  • Page 19 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG...
  • Page 20 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG...
  • Page 21 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG...
  • Page 22: Wiring Diagram

    CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 7 Wiring Diagram...
  • Page 23 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG...
  • Page 24 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG...
  • Page 25 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG...
  • Page 26: Operation Details

    CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 8 Operation Details 8.1. Cooling Mode Operation Cooling in operation according to Remote Control setting. Time Delay Safety Control (3 minutes) • When the compressor is stopped by Remote Control, it restarts after 3 minutes when the Remote Control is turned ON.
  • Page 27 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG Automatic Fan Speed Mode When Automatic Fan Speed is selected at Remote Control during cooling operation. • Fan speed rotates in the range of Hi to Me.
  • Page 28 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 8.2. Soft Dry Mode Operation • The unit starts cooling operation until the room temperature reaches the setting temperature set on the Remote Control, and then Soft Dry operation will start.
  • Page 29 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG Soft Dry Operation Time Diagram...
  • Page 30 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 8.3. Air Circulation Mode Operation • When the temperature near the ceiling reaches the setting temperature, Air Circulation Mode operation commences at low airflow volume. It stops when the temperature drops to 2°C below the setting temperature.
  • Page 31 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 8.5. Sleep Mode Auto Operation Cooling or Soft Dry Operation Purpose is to obtain a comfortable room temperature while sleeping. When you press the SLEEP Mode, the following movement will start to avoid overcooling.
  • Page 32 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 8.8. Random Auto Restart Control • If there is a power failure, operation will be automatically restarted after 3 to 4 minutes when the power is resumed.
  • Page 33 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 8.10. Vertical Airflow Direction Control Vertical Airflow Direction Auto-Control • When set a Airflow Direction Auto-Control with remote control, the louver swings up and down as shown in the diagram.
  • Page 34: Operating Instructions

    CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 9 Operating Instructions SAFETY PRECAUTIONS Installation Precautions Operation Precautions Before operating, please read the following “Safety Precautions” carefully. Warning Warning To prevent personal injury, injury to others and This sign warns of death or serious injury.
  • Page 35 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG NAME OF EACH PART How to Insert the Batteries 1 Signal Transmitter Remote Control 2 Operation Display 3 Powerful Mode Operation Button 4 Room Temperature Setting Button...
  • Page 36 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG Setting the Fan Speed Setting the Horizontal Airflow Direction Operation Details • Press 4 to select:- – Low Fan Speed COOL – Cooling Operation – Medium Fan Speed •...
  • Page 37 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG CARE AND MAINTENANCE Cleaning the Indoor Unit and Remote Pre-season Inspection Air Purifying Filters Control Is the discharged air cold? • Wipe gently with a soft, dry cloth.
  • Page 38 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG TROUBLESHOOTING Normal Operation Call the Dealer Immediately If the following conditions occur, turn off the main power Is it okay? This is the answer supply, and then call the dealer immediately.
  • Page 39: Installation Instructions

    CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 10 Installation Instructions Required tools for Installation Works 1. Philips screw driver 5. Spanner 9. Gas leak detector 13. Multimeter 2. Level gauge 6. Pipe cutter 10. Measuring tape 14.
  • Page 40 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 1. This equipment must be earthed. It may cause electrical shock if grounding is not perfect. 2. Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of the unit, it may cause fire.
  • Page 41 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG Attached accessories Indoor/Outdoor Unit Installation Diagram Applicable piping kit CZ-3F5, 7AEN (CS-C7BKPG, CS-C9BKPG) CZ-4F5, 7, 10AN (CS-C12BKPG, CS-C14BKPG) SELECT THE BEST LOCATION INDOOR UNIT • There should not be any heat source or steam near the unit.
  • Page 42 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 10.2. INDOOR UNIT 10.2.1. SELECT THE BEST LOCATION 10.2.3. TO DRILL A HOLE IN THE WALL (Refer to “Select the best location” AND INSTALL A SLEEVE OF...
  • Page 43 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 3. For the embedded piping (This can be used for left rear piping & left bottom piping also.)
  • Page 44 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 10.2.5. CONNECT THE CABLE TO THE INDOOR UNIT 1. The inside and outside connecting cable can be connected without removing the front grille. 2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 ×...
  • Page 45 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 10.3. OUTDOOR UNIT HOW TO TAKE OUT FRONT GRILLE Please follow the steps below to take out front grille if 10.3.1. SELECT THE BEST LOCATION necessary such as when servicing.
  • Page 46 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG Connecting the Piping to Outdoor Unit 1. Align the center of the piping and sufficiently tighten the flare nut with fingers. 2. Finally, tighten the flare nut with torque wrench until the wrench clicks.
  • Page 47 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 10.3.4. EVACUATION OF THE EQUIPMENT WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure. 1. Connect a charging hose with a push pin to the Low and High side of a charging set and the service port of the 3-way valve.
  • Page 48 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 10.3.5. CONNECT THE CABLE TO THE OUTDOOR UNIT 1. Remove the control board cover from the unit by loosening the screw. 2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed flexible cord, type designation 245 IEC 57 or heavier cord (4 ×...
  • Page 49: 11 3-Way Valve

    CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 11 3-way Valve 3-way Valve (Liquid Side) 3-way Valve (Gas Side) Works Shaft Position Service Port Shaft Position Service Port Shipping Closed Closed Closed Close (With valve cap)
  • Page 50 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 11.1. Evacuation of the Equipment 11.1.1. Evacuation of the Installation When installing an air conditioner, be sure to evacuate the air inside the indoor unit and pipes in the following procedure.
  • Page 51 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 11.1.2. Pumping down Procedure: 1. Confirm that both the 3-way valves are set to the open 6. Operate the air conditioner at the cooling cycle and position.
  • Page 52 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 11.1.3. Evacuation of Re-installation WHEN REINSTALLING AN AIR CONDITIONER, BE SURE TO If air remains in the indoor unit and refrigeration pipes, it will EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES affect the compressor, reduce to cooling capacity, and could in the following procedure.
  • Page 53 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 11.1.4. Balance refrigerant of the 3-way valves (Lack of refrigerant in the refrigeration cycle) Procedure: 1. Confirm that both the 3-way valves are set to the opened position.
  • Page 54 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 11.1.5. Evacuation (No refrigerant in the refrigeration cycle) Procedure: 1. Connect the vacuum pump to the charge set’s centre hose. 2. Turn on the vacuum pump to evacuate the unit.
  • Page 55 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 11.1.6. Gas charging (After Evacuation) Procedure: 1. Connect the charge hose to the charging cylinder. 4. Immediately disconnect the charge hoses from both 3- way valve service ports.
  • Page 56: Servicing Information

    CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 12 Servicing Information 12.1. Indoor Electronic Controllers Removal Procedures 1. The Electronic Controller, a Signal Receiver and an Indicator (Fig. 3) can be seen by the below steps: •...
  • Page 57 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG − Pulling out the Drain Hose from outlet to remove the Discharge Grille. (Fig. 5) − Removing the right and left screws. (Fig. 5) − Then remove the Control Board by pressing down the hook at the left and pushing up the right hook.
  • Page 58 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG − Remove the screws at the left of the Evaporator. (Fig. 8) Fig. 8 − Remove the Bearing. (Fig. 9) − Push up the Evaporator and pull out the Cross Flow Fan from shaft.
  • Page 59 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG • Remote Control Reset When the batteries are inserted for the first time, or the batteries are replaced, all the indications will blink and the remote control might not work.
  • Page 60: Troubleshooting Guide

    CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 13 Troubleshooting Guide 13.1. Refrigeration cycle system In order to diagnose malfunctions, make sure that there are no electrical problems before inspecting the refrigeration cycle. Such problems include insufficient insulation, problem with the power source, malfunction of a compressor and a fan.
  • Page 61 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 13.1.1. Relationship between the condition of the air conditioner and pressure and electric current Cooling Mode Condition of the air conditoner Low Pressure High Pressure Electric current during operation...
  • Page 62: Technical Data

    CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 14 Technical Data...
  • Page 63 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG...
  • Page 64 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG...
  • Page 65 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 230V Outdoor Temp. (°C) Indoor wet bulb temp. 17.0°C 2.80 2.12 1.05 2.61 2.03 1.13 2.43 1.95 1.21 2.21 1.86 1.31 19.0°C 2.82 1.15 19.5°C 3.07 2.22 1.07...
  • Page 66 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 230V Outdoor Temp. (°C) Indoor wet bulb temp. 17.0°C 4.84 3.67 1.41 4.52 3.52 1.52 4.21 3.38 1.62 3.83 3.21 1.75 19.0°C 4.88 1.54 19.5°C 5.31 3.84 1.44...
  • Page 67 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 230V Outdoor Temp. (°C) Indoor wet bulb temp. 17.0°C 3.57 2.71 1.11 3.34 2.60 1.19 3.10 2.49 1.28 2.82 2.37 1.38 19.0°C 3.60 1.21 19.5°C 3.92 2.83 1.13...
  • Page 68 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 230V Outdoor Temp. (°C) Indoor wet bulb temp. 17.0°C 3.52 2.67 1.15 3.29 2.56 1.23 3.06 2.46 1.32 2.78 2.34 1.42 19.0°C 3.55 1.25 19.5°C 3.87 2.80 1.17...
  • Page 69: Exploded View

    CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 15 Exploded View Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 70: Replacement Parts List

    CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 16 Replacement Parts List <Model: CS-C7BKPG / CS-C9BKPG / CS-C12BKPG> REF. PART NAME & DESCRIPTION QTY. CS-C7BKPG CS-C9BKPG CS-C12BKPG REMARKS ← ← CHASSY COMPLETE CWD50C1177 ← ←...
  • Page 71: Exploded View

    CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 17 Exploded View Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 72: Replacement Parts List

    CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 18 Replacement Parts List <Model: CU-2C14BKP5G> DESCRIPTION & NAME Q’TY CU-2C14BKP5G REMARKS CHASSY ASS’Y CWD50K573A SOUND PROOF BOARD CWH15066 FAN MOTOR BRACKET CWD54168 CONDENSER CWB32C1030 FAN MOTOR...
  • Page 73: Exploded View

    CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 19 Exploded View Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 74: Replacement Parts List

    CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 20 Replacement Parts List <Model: CU-2C18BKP5G> DESCRIPTION & NAME Q’TY CU-2C18BKP5G REMARKS CHASSY ASS’Y CWD50K663A AIR GUIDER FOR PROPELLER FAN CWD31094A SOUND PROOF BOARD CWH15071 FAN MOTOR BRACKET...
  • Page 75 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 21 Exploded View Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 76 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 22 Replacement Parts List <Model: CU-3C20BKP5G> DESCRIPTION & NAME Q’TY CU-3C20BKP5G REMARKS CHASSY ASS’Y CWD50K663A COMPRESSOR 2PS193D2AA01 AIR GUIDER CWD31094A SOUND PROOF BOARD CWH15071 FAN MOTOR BRACKET...
  • Page 77 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 23 Exploded View Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 78 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 24 Replacement Parts List <Model: CU-2C19BK> DESCRIPTION & NAME Q’TY CU-2C19BKP5G REMARKS BASE ASS’Y CWD50K662A COMPRESSOR A 2KS224D5CA02 MOUNT RUBBER CWH50055 CWH4582065 SOUND PROOF MATERIAL CWG30915 COMPRESSOR B...
  • Page 79 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 25 Electronic Parts List <Electronic Controller Part No.: CWA742779, CWA742780 & CWA742781> SYMBOL DESCRIPTION & NAME PART NO. BZ101 SOUND GENERATOR A48040 C-FM SH CAPACITOR A31698 D08, D10, D11 DIODE B0ACCK000005 (CWA742779 &...
  • Page 80 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 26 Electronic Circuit Diagram • CS-C9BKPG / CU-2C14BKP5G • CS-C9BKPG / CU-2C18BKP5G • CS-C9BKPG / CU-3C20BKP5G • CS-C7BKPG / CU-2C19BKP5G CS-C12BKPG SCHEMATIC DIAGRAM 1/7 MAIN RECEIVER (CR3)
  • Page 81 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG SCHEMATIC DIAGRAM 2/7 4.7k SSR01 DB01 P50/A8 – P51/A9 TIMER SHORTEN RY-PWR DRIVE SIGNAL STEPPING 4.7k MOTOR FAN SPEED P52/A10 P03/INTP3 DRIVE DRIVE SIGNAL SIGNAL P53/A11 P02/INTP2...
  • Page 82 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG SCHEMATIC DIAGRAM 3/7 OUTDOOR UNIT THERMAL FUSE 102°C (WHT) RY-PWR FUSE 250V 0.047µ IC04 IC03 ZNR01 REGULATOR REGULATOR 511U SSR01 ZNR03 125µH 3300µ 470µ 100µ 511U –...
  • Page 83 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG • CU-2C14BKP5G SCHEMATIC DIAGRAM 4/7 COMPRESSOR A V-COIL COMPLETE MOTOR CAPACITOR ELECTRONIC COMP-A CAPACITOR (GRN) AC(WHT) (WHT) CONTROL DEVICE VH7-4 CN-V FM(YEL) FM(BLU) RY-CA FUSE 3.15A 250V Ω120...
  • Page 84 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG • CU-2C18BKP5G SCHEMATIC DIAGRAM 5/7 INDOOR UNIT AC 220-230-240 V 50 Hz TO INDOOR SINGLE PHASE UNIT B OUTDOOR UNIT TERMINAL YELLOW BLUE MARK COMPRESSOR TERMINAL CAPACITOR A...
  • Page 85 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG • CU-3C20BKP5G SCHEMATIC DIAGRAM 6/7 COMPRESSOR A COMPRESSOR B OLP A OLP B V-COIL COMPLETE MOTOR CAPACITOR CAPACITOR ELECTRONIC CAPACITOR COMP-A (GRN) AC(WHT) COMP-B CONTROL DEVICE VH7-4...
  • Page 86 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG • CU-2C19BKP5G SCHEMATIC DIAGRAM 7/7 INDOOR UNIT AC 220-230-240 V 50 Hz TO INDOOR SINGLE PHASE UNIT B OUTDOOR UNIT TERMINAL YELLOW BLUE MARK COMPRESSOR TERMINAL CAPACITOR A...
  • Page 87 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG...
  • Page 88 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG How to use electronic circuit diagram TIMER TABLE Test Mode Name Time (When test point Remarks Short-circuited) Sleep Mode Waiting 1 hr. 6 sec. Sleep Mode Operation 8 hrs.
  • Page 89 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 26.1. REMOTE CONTROL...
  • Page 90 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 26.2. PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD TOP VIEW...
  • Page 91 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 26.3. PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD BOTTOM VIEW...
  • Page 92 CS-C9BKPG CU-2C14BKP5G / CS-C9BKPG CU-2C18BKP5G / CS-C9BKPG CU-3C20BKP5G / CS-C7BKPG CU-2C19BKP5G / CS-C12BKPG 26.4. PRINT PATTERN OUTDOOR UNIT PRINTED CIRCUIT BOARD CU-2C14BK / CU-3C20BK [MACC] Printed in Malaysia...

Table of Contents