Mitsubishi Electric MU-GA50VB Service Manual page 33

Split-type, air conditioners wireless type models
Hide thumbs Also See for MU-GA50VB:
Table of Contents

Advertisement

OPERATING PROCEDURE
3. Removing the outdoor fan motor
(1) Remove the cabinet. (Refer to 1.)
(2) Disconnect the connector and remove the hocked lead
wire from the fan motor.
(3) Remove the propeller nut and remove the propeller.
(4) Remove the screws fixing the fan motor.
(5) Remove the outdoor fan motor.
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1.)
(2) Remove the soundproof felt.
(3) Remove the terminal cover on the compressor.
(4) Disconnect the lead wires from the glass terminal of the
compressor.
(5) Recover gas from the refrigerant circuit.
NOTE:
Recover gas from the pipes until the pressure gauge
shows 0 kg/cm
(6) Disconnect the welded part of the discharge pipe.
(7) Disconnect the welded part of the suction pipe.
(8) Remove nuts fixing the compressor.
(9) Remove the compressor.
2
(0MPa).
Photo 4
Propeller
Photo 5
Discharge
pipe
Compressor
33
PHOTOS
Hook
Propeller nut
Compressor set nuts
Suction
pipe

Hide quick links: