3-2. ELECTRICAL PARTS SPECIFICATIONS
Model
Parts name
Thermistor
(Room temperature
detection)
Thermistor
(Pipe temperature
detection/ Liquid)
Thermistor
(Pipe temperature
detection/ Gas)
Fuse
(Indoor controller board)
Fan motor
(with Thermal fuse)
Fan motor capacitor
Vane motor
Drain pump
Drain sensor
Linear expansion valve
[coil]
Electric heater
(Condensation proof)
Power supply terminal
block
Transmission terminal
block
MA remote controller
terminal block
Note: Refer to WIRING DIAGRAM for the supplied voltage.
Symbol
PLFY-P20VCM-E2.TH
TH21
Resistance 0 /15k , 10 /9.6k , 20 /6.3k , 25 /5.4k , 30 /4.3k , 40 /3.0k
TH22
Resistance 0 /15k , 10 /9.6k , 20 /6.3k , 25 /5.4k , 30 /4.3k , 40 /3.0k
TH23
Resistance 0 /15k , 10 /9.6k , 20 /6.3k , 25 /5.4k , 30 /4.3k , 40 /3.0k
FUSE
6-pole OUTPUT 11W
PK6V11-LF
MF
1.0
× 440V
C
MV
DP
Thermistor resistance 0 /6k , 10 /3.9k , 20 /2.6k , 25 /2.2k , 30 /1.8k , 40 /1.3k
DS
DC12V Stepping motor drive, Port dimension 5.2 (0~2000pulse)
LEV
H2
TB2
TB5
TB15
PLFY-P25VCM-E2.TH
PLFY-P32VCM-E2.TH
250V 6.3A
6-pole OUTPUT 15W
6-pole OUTPUT 20W
PK6V15-LD
Thermal fuse
OFF 145
1.5
× 440V
MSBPC20M13
DC12V 300 /phase
PLD-12230ME-1
INPUT 12/10.8W 24 /Hr
EDM-40YGME
240V 15W
(L, N,
) Rated to 330V 30A
(M1, M2, S) Rated to 250V 20A
(1, 2) Rated to 250V 10A
10
PLFY-P40VCM-E2.TH
6-pole OUTPUT 20W
PK6V20-LL
PK6V20-LM
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Plfy-p32vcm-e2.thPlfy-p25vcm-e2.thPlfy-p40vcm-e2.th