7-4 Refrigerating Cycle Block Diagram

INDOOR UNIT
Allowavle pipe length:Maximum 15m
Allowable pipe drop distance:Maximum 10m
Capillary tube
Heat
exchanger
(Evaporator)
*
Amount of refilling per extension length of 1m;
When extending the pipe length by more than 5m, 40g of R-22 refrigerant should be refilled per
extension length of 1m.

Refrigerating cycle temperature and pressure

Operating Condition
Standard
Max over load
Cooling
Low temp
Standard
Heating
Max over load
Deice
7-4
3-way valve
Liquid side
Gas side
3-way valve
STD Pressure
Piping Temp.
(kg/cm
2
G)
T1
(GAS SIDE)
4.5~5.5
40~45
6.5~7.5
50~55
3~4
30~35
18.5~20.5
32~36
-
36~40
-
28~32
OUTDOOR UNIT
Check valve
Capillary tube
Heat
exchanger
(Condenser)
4-way valve
Compressor
Use Temp. Condition (°C)
Indoor
T2
DB
WB
9~12
27
14~18
32
1~4
21
65~75
20
70~80
27
40~45
20
Cooling
Heating
Gas leak check point
Outdoor
DB
WB
19
35
24
23
43
26
16
21
16
-
7
6
-
21
16
-
2
1