Fujitsu AB*14LBAJ Service Instruction page 61

Split type room air conditioner universal floor / ceiling duct / cassette/ wall mounted / floor type inverter multi
Hide thumbs Also See for AB*14LBAJ:
Table of Contents

Advertisement

Trouble shooting 18
OUTDOOR UNIT Error Method:
Outdoor Unit Fan Motor Error
Detective Actuators:
Outdoor Unit Main PCB Circuit
Outdoor Fan Motor
Forecast of Cause:
1. Fan rotation failure
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
OK
Check Point 2 : Check ambient temp. around motor
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
OK
Check Point 3 : Check Output Voltage of Main PCB
Check outdoor unit circuit diagram and the voltage.
(Measure at Main PCB side connector)
RED
1
2
3
BLACK
CN800
4
WHITE
5
YELLOW
6
BROWN
7
Read wire
Red - Black
White - Black
If the voltage is not correct, replace Main PCB.
Indicate or Display:
Refer to error code table.
Detective details:
When outdoor fan rotation speed is less than 100rpm in 20 seconds
after fan motor starts, fan motor stops.
After fan motor restarts, if the same operation within 60sec is repeated
3 times in a row, compressor and fan motor stops.
If
permanently.
2. Motor protection by surrounding temperature rise
FAN MOTOR
FM
DC voltage
300
•`
400V
15 1.5V
and
repeats 5 times in a row, compressor and fan motor stops
02-28
3. Main PCB failure

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents