Mitsubishi Electric Mr.Slim MUZ-GC25NA - C1 Service Manual page 32

Outdoor unit split-type air conditioners
Table of Contents

Advertisement

Indication
No.
Symptom
LED2
LED1 (Red)
(Yellow)
Outdoor unit
Once
Lighting
operates.
20
Twice
Lighting
21
3 times
Lighting
22
4 times
Lighting
23
5 times
Lighting
24
Outdoor unit
9 times
Lighting
operates
25
Lighting
Lighting
26
Abnormal point /
Condition
Primary current protection The input current exceeds 15 A.
Secondary current protec-
The current of the compressor exceeds 15 A.
tion
High-pressure protection The indoor gas pipe temperature exceeds 45°C during heating.
Defrosting in cooling
The indoor gas pipe temperature falls 3°C or below during cooling.
Discharge temperature
The discharge temperature exceeds 100°C during operation.
protection
Low discharge tempera-
The frequency of the compressor is kept 80 Hz or more and the dis-
ture protection
charge temperature is kept under 39°C for more than 20 minutes.
Cooling high-pressure
The outdoor heat exchanger temperature exceeds 58°C during op-
protection
eration.
Inverter check mode
The unit is operated with emergency operation switch.
Normal
-
Condition
32
Correspondence
These symptoms do not mean any ab-
normality of the product, but check the
following points.
• Check if indoor fi lters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circu-
lation is short cycled.
• Check refrigerant circuit and refriger-
ant amount.
• Refer to 9-5
.
"Check of LEV".
.
• Refer to 9-5
"Check of outdoor
thermistors".
.
• Refer to 9-5
"Check of LEV".
• Check refrigerant circuit and refriger-
ant amount.
This symptom does not mean any ab-
normality of the product, but check the
following points.
• Check if indoor fi lters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circu-
lation is short cycled.
-
-