Mitsubishi Electric PUHZ-P100VHA2 Service Manual page 97

Mitsubishi electric split-type, heat pump air conditioners
Hide thumbs Also See for PUHZ-P100VHA2:
Table of Contents

Advertisement

SW2 setting
LEV-A opening pulse on error occurring
0 - 480
ON
1
2 3 4 5 6
Indoor room temperature (TH1) on error
occurring
ON
8 - 39
1
2 3 4 5 6
Indoor pipe temperature/Liquid (TH2) on
error occurring
−39 - 88
ON
1
2 3 4 5 6
Indoor pipe temperature/Cond./Eva.
(TH5) on error occurring
−39 - 88
ON
1
2 3 4 5 6
Outdoor pipe temperature/2-phase (TH6)
on error occurring
−39 - 88
ON
1
2 3 4 5 6
Outdoor outside temperature (TH7) on
error occurring
−39 - 88
ON
1
2 3 4 5 6
Outdoor heatsink temperature (TH8) on
error occurring
−40 - 200
ON
1
2 3 4 5 6
OCH415F
Display detail
97
The black square (■) indicates a switch position.
Explanation for display
0 - 480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 130 pulse;
0.5 secs.
8 - 39
−39 - 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs.
−39 - 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs.
−39 - 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs.
−39 - 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs.
−40 - 200
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
0.5secs.
2 secs.
1
30
0.5secs.
2 secs.
15
0.5secs.
2 secs.
15
0.5secs.
2 secs.
15
0.5secs.
2 secs.
15
Unit
Pulse
:
:
:
:
:
: