Advertisement

(2) Functions available when setting the unit number to 01-03 or AL (07 in the case of wireless remote controller)
• When setting functions for an indoor unit in an independent system, set the unit number to 01 referring to 4 setting the
indoor unit number of Operating Procedure.
• When setting functions for a simultaneous- Twin Triple indoor unit system, set the unit number to 01 to 03 for each indoor unit
in the case of selecting different functions for each unit referring to 4 setting the indoor unit number of Operating Procedure.
• When setting the same functions for an entire simultaneous Twin Triple-indoor unit system, set refrigerant address to AL (07
in the case of wireless remote controller) referring to 4 setting the indoor unit number of Operating Procedure.
Function
Filter sign
100h
2500h
No filter sign indicator
Quiet
Air flow
Standard
( Fan speed )
High ceiling
No.of air outlets
4 directions
3 directions
2 directions
Optional high efficiency Not supported
Supported
filter
No vanes ( Vane No.3 setting : PLA only )
Vane setting
Vane No.1 setting
Vane No.2 setting
Not supported
Optional humidifier
( PLA only )
Supported
Vane differential setting No.1 setting ( TH5: 24-28 )
No.2 setting ( Standard , TH5:28-32 ) 14
in heating mode
( cold wind prevention )
No.3 setting ( TH5: 32-38 )
Swing
Not available Swing
Available
Set temperature in heating Available
mode ( 4 deg up ) *1
Not available
Fan speed during the
Extra low
Stop
heating thermo OFF
Set fan speed
Set fan speed
Fan speed during the
Stop
cooling thermo OFF
Detection of abnormality of Available
the pipe temperature ( P8 ) Not available
*1. PKA-HAL/KAL: 2 deg up
PEAD-RP
JA(L)
Function
Filter sign
100h
2500h
No filter sign indicator
External static pressure 35/50/70/100/150Pa
External static pressure 35/50/70/100/150Pa
Set temperature in heating
Available
mode ( 4 deg up )
Not available
Fan speed during the
Extra low
heating thermo OFF
Stop
Set fan speed
Fan speed during the
Set fan speed
cooling thermo OFF
Stop
Detection of abnormality
Available
of the pipe
Not available
OCH415F
Setting
Mode
Settings
No.
No.
1
07
2
3
1
08
2
3
1
09
2
3
1
10
2
1
11
2
3
1
13
2
1
2
3
}
1
PLA-BA
23
2
Wave air flow
1
24
2
1
25
2
3
1
27
2
1
28
2
Mode
Setting
Settings
No.
No.
07
08
Refer to the right table
10
24
25
27
28
: Initial setting ( Factory setting )
4-Way
Ceiling
Ceiling suspended
cassette
concealed
PEAD-EA(2)
PLA-BA
PCA-GA(2)
PCA-KA
PEAD-GA
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
: Initial setting
External static
( Factory setting )
1
35Pa
2
50Pa
70Pa
3
100Pa
Refer to the right table
150Pa
1
2
1
2
3
1
2
1
2
100
- : Not available
Wall
mounted
PKA-GAL
PCA-HA
PKA-HAL PKA-KAL
PKA-FAL(2)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Setting No.
pressure
Mode No. 08 Mode No. 10
1
2
3
1
1
2
2
2
3
2
Floor
standing
PSA-GA
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Initial setting
( Factory setting )