Lennox EL195UHE Elite Series Installation Instructions Manual page 35

Elite series gas furnace upflow / horizontal air discharge
Hide thumbs Also See for EL195UHE Elite Series:
Table of Contents

Advertisement

IMPORTANT
When combining the furnace and evaporator
coil drains together, the A/C condensate drain
outlet must be vented to relieve pressure in or-
der for the furnace pressure switch to operate
properly.
Condensate Trap With Optional Overflow Switch
From Evaporator Coil
HorizontalFurnace4" Min. to 5" Max.above
Optional
FIGURE 55
Evaporator
Drain Pan
Piping from furnace and evaporator coil must slope down a minimum 1/4" per ft. toward trap
condensatedrain connection)
FurnaceCondensate
Drain Connection
EL195UHE with Evaporator Coil Using a Common Drain
(Unit shown in horizontal left−hand discharge position)
Coil
EL195UHE with Evaporator
Coil Using a Common Drain
(1" min. to 2" Max.above
condensatedrain connection)
Condensate
Drain Connection
4"min
5"max
5' max.
PVC Pipe Only
FIGURE 57
Page 35
Evaporator drain
line required
FIGURE 56
(4" min. to 5" Max.above
condensatedrain connection)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents