d. On Delay is the time, in seconds, the unit waits before switching an outlet on.
e. Off Delay is the time, in seconds, the unit waits before switching an outlet off.
f. Reboot Delay is the time, in seconds, the unit waits before rebooting an outlet.
g. Reboot Hold Delay is the time, in seconds, the unit waits after switching the
outlet off, but before switching an outlet on during a reboot.
h. Power-On Action describes the state the outlet will start at power-on (On, Off
or Last).
i. Power-On Delay is the time, in seconds, the unit waits after power-on before
performing the power-on action for the outlet.
3. Click the Save button if any settings are changed.
Device Operation:
1. Click the Operation icon.
2. Select the operation you wish to perform:
On/Off turns on/off all outlets.
For outlets currently on, Reboot cycles the outlets off, then back on after the
reboot hold delay. For outlets currently off, Reboot turns the outlets on.
Cancel will cancel the current operation if it has not been completed yet.
Reset kW Hours will reset the total Energy measured in kWh.
Caution: These actions affect the entire device.
3. For operations involving the state of the outlets, setting Delay to True will use the
current Delay configuration for each outlet when performing the selected
operation.
4. Select Submit to issue the action.