Operational Frequency Control Of Outdoor Unit; Pre-Heat Control - Mitsubishi Electric MSC-GE-VB Service Manual

Split-type
Hide thumbs Also See for MSC-GE-VB:
Table of Contents

Advertisement

2. Maximum/minimum frequency in each operation mode
Applied model
MUZ-GC25
MUZ-GC35
MUZ-HC25
MUZ-HC35
MUZ-FD25
MUZ-FD35VA
MUZ-FD35VAH/VABH
MUZ-FD50
MUZ-GE25
MUZ-GE35
MUZ-GE42
MUZ-GE50
MUZ-GE60
MUZ-GE71
MUZ-EF25
MUZ-EF35
MUZ-EF42
MUZ-EF50
The operation frequency in COOL mode is restricted by the upper limit frequency after 0.5 - 1 hour as shown below for
dew prevention. It is rated frequency or less.
Upper limit
frequency

2-10. PRE-HEAT CONTROL

1. Outline
Compressor is energized to improve the start-up of compressor at a low outside temperature even when compressor
is stopped.
2. Pre-heat control
MUZ-GC/HC/FD/GE
Compressor
Pre-heat control
Defrost thermistor
Pre-heat control ON condition
(1) Compressor is not operating. (However, pre-heat control is still OFF for 30 minutes after compressor is stopped,
regardless of the outside temperature.)
(2) Defrost thermistor reads 20°C or below.
Defrost thermistor monitor hourly, and when defrost thermistor reads 20°C or below, pre-heat control is turned ON.
When pre-heat control is turned ON, compressor is energized about 50 W (40-60 W). (Compressor and fan are not operated.)
COOL
Minimum
Maximum
32
85
32
98
28
85
28
98
10
52
10
62
10
62
20
85
24
93
20
98
10
90
20
98
20
104
26
120
28
93
20
98
10
90
20
98
Maximum
frequency
Rated frequency or less
0.5 - 1 hour
ON
OFF
ON
OFF
20 °C
30 minutes 1 hour
Operational frequency (Hz)
HEAT
Minimum
Maximum
28
105
48
105
28
105
28
98
18
90
18
90
18
115
20
130
32
105
32
98
18
115
20
108
30
117
26
124
30
105
30
98
18
100
20
108
Time
21
DRY
Minimum
Maximum
32
41
32
58
28
41
28
41
28
41
28
41
28
41
20
45
48
38
55
38
35
54
20
98
20
104
26
120
28
48
20
55
10
54
20
83