System Component Details; Protective Boards With Z Profiles; Deflector - Viessmann Vitolig 200 Technical Manual

Solid fuel boiler 5 to 40 kw
Table of Contents

Advertisement

3 Vitolig 300

System component details

Protective boards with Z profiles

A
A Z profile (length 2000 mm)
B Protective board (30 mm thick
on−site provision)
C Fire door T 30 or T 90

Deflector

A
*1
Blow inlet approx. 4 5 m
A Fill adaptor
B Deflector (1500 x 1500 mm)
14
B
A
C
>100 mm
Z profiles are available as accessories for
the installation of the protective boards.
Do not install Z profiles up to the ceiling
to permit the removal or addition of the
protective boards.
The deflector should be installed at a
distance of at least 100 mm from the wall
opposite the filling adaptor (see adjacent
diagram). This deflector protects the
pellets as well as the brickwork or the
rendering/plaster.
Plaster/rendering or pieces of brick that
have been dislodged can block the
suction wands and the pellet worm−drive
B
or the burner tray ash removal of
Vitolig 300.