6. Electric Characteristics
Model
Type
AUUW126B
(UU12W UEB)
AUUW186B
(UU18W UEB)
AUUW246B
(UU24W UEB)
AUUW306B
inverter
(UU30W UEB)
AUUW366B
(UU36W UEB)
AUUW4860
(UU48W UYB)
AUUW6060
(UU60W UYB)
Notes :
1. Voltage range
Voltage supplied to the unit terminals should be within the mini-
mum and maximum range
2. Maximum allowable voltage unbalance between phase is 2 %
3. MCA / MOP
MCA = (1.25 x Load1) + Load2 + Load3
MOP = (2.25 x Load1) + Load2 + Load3
- Load1 : Rated running current of largest motor
(compressor or other motor)
- Load2 : sum of current for all other motors
- Load3 : any other load rated 1.0A or more
4. Select wire spec. based on the MCA
5. Recommended circuit breaker is ELCB (Earth Leakage circuit
breaker)
6. MSC & RLA are measured as the compressor only test condi-
tion.
7. MSC values
10/28 : MSC of (inv. comp.) / (const. comp.)
Unit
Hz
Voltage
Voltage range
Min. : 198
220~240
50
Max. :264
Power
Compressor
MCA
MOP
MSC
8.13
14.6
10
13.2
23.9
10
17.1
30.8
10/25
24.6
44.3
10/28
30.3
53.4
10/63
36.0
63.3 10/28/28 7.0/8.2/8.2
46.2
81.7 10/28/63 7.0/8.2/14.0
8. RLA is measured during each individual compressor test condi-
tion.
Ex) 7.0/8.2 : RLA of (inv. comp.) / (const. comp.)
9. OFM is measured as the outdoor unit test condition
(Example) Selection of proper circuit breaker
Model : AUUW126B
- Rated running current : 6.5 A (refer to spec. sheet)
MCA = (1.25 x Load1) + Load2 + Load3
= (1.25 x 6.5) + 0 + 0 = 8.13 A
MOP = (2.25 x Load1) + Load2 + Load3
= (2.25 x 6.5) + 0 + 0 = 14.6 A
Finally select circuit breaker 15A(Min. circuit breaker is 15A)
MCA : Minimum Circuit Amperes (A)
MOP : Maximum rating over current protective device
MSC : Maximum Starting Current
RLA : Rated Load Amperes (A)
OFM : Outdoor Fan Motor
kW : Fan Motor rated output (kW)
FLA : Full Load Amperes (A)
MPS Inverter SINGLE A
OFM
RLA
kW
FLA
7.0
0.12
0.68
7.0
0.12
0.68
7.0/6.0
0.14
0.73
7.0/8.2
0.16
0.92
7.0/14.0
0.24
1.46
0.4
1.87
0.4
1.87
Service Manual 89