Mitsubishi Electric EHST20C-VM2C.UK Service Manual page 47

Cylinder unit
Table of Contents

Advertisement

Error code
Title and display conditions
P1/P2/L5/LD
Indoor unit temperature thermistor failure
* The thermistors subject to failure can be checked
in "Request code: 567" in "Running information
<DHW/Heating/LP/FS/OS>
Error code displayed when thermistor is at open or
short (see table).
Exceptions
Error code will not be displayed for TH2; During
defrost and for 10 minutes after defrost operation.
Error code
Symbol
P1
TH1A/TH1B
P2
TH2
THW1
THW2
THW5
L5
THW6
THW7
THW8
THW9
THWB1
LD
THWB2
L6
Circulation water freeze protection
<DHW/Heating/LP/FS/OS>
Error code displayed when THW1 detects a
temp. ≤ 1ºC for 10 consecutive seconds or
THW2 detects a temp. ≤ 3ºC for 10 consecutive
seconds.
Exception
Error code will not be displayed if;
FS function is disabled,
For 10 minutes after water circulation pump1 is
switched on.
OCH570
Possible Cause
1.
Connector/terminal wire has become
detached or loose wiring.
2.
Thermistor fault
3.
FTC board failure
4.
The thermistor on the wireless remote
controller or the main remote control-
ler may be defective. (when Room
temp. is chosen for the Heating opera-
tion and when Main Controller or
Room RC 1-8 is chosen for the Room
Sensor setting in the Initial setting)
5.
Incorrect setting of the DIP switch(es)
Thermistor
Name
Room temperature thermisitor
Liquid temperature thermisitor
Flow water temperature thermisitor
Return water temperture thermisitor
Tank water temperture thermisitor
Zone 1 flow water temperature thermistor
Zone 1 return water temperature thermistor
Zone 2 flow water temperature thermistor
Zone 2 return water temperature thermistor
Boiler flow water temperature thermistor
Boiler return water temperature thermistor
1. Insufficient system head
2. Reduced flow in primary water circuit
Due to 1 or more of the following;
Faulty pump, insufficient air purge,
blocked strainer, leak in water circuit
3. Valve operation fault
4. 2-way valve (local supply) actuator
fault
5. 3-way valve actuator fault
6. THW1 has become detached from its
holder.
7. THW1 or THW2 fault
8. FTC board failure
47
Diagnosis and action
1.
Visually check the terminals and connec-
tions and reattaches appropriate.
2.
Check resistance of thermistor against
table in section 10-6.
Compare FTC detected temperature to
hand held detector.
3.
Replace board.
4.
Replace wireless remote controller or main
remote controller.
5.
Check the DIP switch setting(s).
Open detection
Short detection
-39ºC or below
88.5ºC or above
-39ºC or below
88.5ºC or above
-39ºC or below
88.5ºC or above
-39ºC or below
88.5ºC or above
-39ºC or below
88.5ºC or above
-39ºC or below
88.5ºC or above
-39ºC or below
88.5ºC or above
-39ºC or below
88.5ºC or above
-39ºC or below
88.5ºC or above
-40ºC or below
140ºC or above
-40ºC or below
140ºC or above
1. Refer to table in section 10-6. to determine
if system pump meets requirements.
If more head required either add an pump
of the same size or replace existing pump
with capacity model.
See 11. DISASSEMBLY PROCEDURE for
how to replace pump.
2. Check circulation pump (See 10-6. for how
to check).
Open purge valve to remove trapped air.
Check the strainer for blockages.
Check the primary water circuit for leaks.
Check that the flow amount is within the
recommended range.
3. Check valves on primary water circuit are
installed level.
4. Electrically test to determine fault.
5. 1) Electrically test to determine fault.
2) Operate 3-way valve manually using the
main remote controller. (Refer to
<Manual operation> in 9-4).
3) Replace 3-way valve coil.
4) Replace 3-way valve. (Refer to Procedure
6 in "11. DISASSEMBLY PROCEDURE."
6. Visually inspect location and reattach as
necessary.
7. Check resistance of thermistor against table
in section 10-6.
Compare FTC detected temperature to
hand held detector.
8. Replace board.