INSTALLATION AND INSTRUCTION MANUAL
FOR CR200 DEHUMIDIFIER.
PRODUCTION NUMBER :
STOCK NUMBER: 100062
DOCUMENT NO.: 200-06E
01.11.00
H
B
D
E
Postgiro:
466-0722
CVR-nr./VAT-no.:
15 20 03 32
PAGE
CONTENTS :
1
1.
Principle of operation
3
2.
Applications
4
3.
Dimensions, in and outlet connections
5
4.
Technical data, specifications
6
5.
Components diagram, main components
8
6.
Capacity diagram
7.
Electric features :
9
7.1 Scematic electrical diagram
10
7.2 Wiring in cabinet
11
7.4 Electric components
11
7.5 Connection of humidistat
12
7.6 Electric connection, energy consumption
12
8.
Installation
13
9.
Fan curves, airflow/pressure
14
10.
Start-up procedure
15
11.
Maintenance
16
12.
Trouble shooting
17
13.
Service/repair
18
14.
Sound level
19
15.
Reg.duct system (option)
H
U
M
I
D
I
Bank:
Caspar Brands Plads 9, 4220 Korsør
& air flows.
F
I
C
A
T
I
Danske Bank
Konto/Acc:
Swift:
HB COTES A S
O
N
S
Y
S
Internet:
3212 3212298972
E-mail:
DABADKKK
Værkstedsvej
5
DK-
Skælskør
4230
Tel +
45 58 19 63 22
Fax +
45 58 19 58 44
T
E
M
S
www.hbcotes.com
dehum@hbcotes.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CR200 and is the answer not in the manual?

Questions and answers

Summary of Contents for Cotes CR200

  • Page 1 HB COTES A S Værkstedsvej Skælskør 4230 Tel + 45 58 19 63 22 Fax + 45 58 19 58 44 INSTALLATION AND INSTRUCTION MANUAL FOR CR200 DEHUMIDIFIER. PRODUCTION NUMBER : STOCK NUMBER: 100062 DOCUMENT NO.: 200-06E PAGE CONTENTS :...
  • Page 2: Principle Of Operation

    - the diagram shows then dry air condition of X= 3,7 g/kg - removed per kg air is then: 8,7 - 3,7 = 5,0 g/kg Capacity CR200 at this condition: Dry air flow is nominal 200 m3/h = (x 1,2) = 240 kg/h...
  • Page 4: Applications

    Page 3 2. APPLICATIONS. Dehumidifiers in the CR range are used for dehumidification of ambient air at normal atmospheric pressure. This can be an installation for moisture control in an unheated store room, in a water work building, production room for hygro- scopic materials...
  • Page 6: Further Specifications

    Page 5 4. TECHNICAL DATA, SPECIFICATIONS CR200. Dry air, free blowing .... : 290 m3/h Dry air, nominal ....: 200 m3/h Reg.-air, nominal ....: 65 m3/h External pressure, dry air (at 160): 160 Pa External pressure, reg.-air (at 50): 150 Pa Capacity at 20C, 60%RH ...
  • Page 8 Page 7 4. COMPONENTS DIAGRAM, CR200. (ref. to drawing R2127) PCS. STOCK.NO DESCRIPTION. 121109 Connection for reg.outlet, ø80 123001 Cabinet back plate 123003 Filter & fan Box Cover for filter 123002 Cabinet, top plate 127004 Pulley SPZ63-1 132103 Drive belt Ø6/1050...
  • Page 12: Wiring In Cabinet

    Page 11 7.4 Electric components CR200. Refers to electric diagrams: R2223 .. : Electric diagram R2224 .. : Wiring in cabinet SA1 110215: Selector switch, Manual, 0, Automatic. Sälzer P220-61025E219M. 20A. KT1 111833: Relay, Finder 60.13, 230V/50, 10A (AC1) 111851: Finder socket 90.73 for relay and timer 111822: Finder timer 86.60, delay 30S...
  • Page 13: Installation

    The humidistat should be approved for 230V/10A (ex. our Jumo Compact spec., stock no. 140510). 7.6 Electric connection. The dehumidifier CR200 is connected 230V, 1N+PE. Connection to the terminals U1,N,PE, placed into the outside connec- tion box on the front of the dehumidifier.
  • Page 15 You should then contact your supplier before installation for advice. See fan curves, page 13. 10. COMMISIONING CR200, 10.1 ELECTRIC. Before starting-up the dehumidifier, check that all electric connections are made correctly.
  • Page 16 Page 15 The amps is adjusted on the damper in the reg.air inlet ducts (see drawing R2232, page 19). Adjusted value must be 8,0A. If stabilised at a higher value, the damper must be clo- sed until 8A is indicated. If stabilised at a lower value, the damper must be ope- ned until 8A is indicated.
  • Page 17: Maintenance

    Page 16 11. MAINTENANCE. Dehumidifier CR200 only needs a minimum of maintenance. All components are service free, which means no lubrication or adjustment. Only three things should be checked under normal operati- - air filters should be checked or replaced at least every 3 mth.- depending on the pollution of the air.
  • Page 18: Safety Instruction

    Page 17 12.4 If the desired humidity is not obtained, the problem can be the dehumidifier - or the other parts in the total installation ( room tightness, humidistat...). To verify this, check: - rotation of rotor ? - the dry air should be 15-20C warmer than the inlet main air.
  • Page 19: Sound Level

    Ø100 is installed too. The sound level is then measured 1m outside the cabinet, and 1,6m above the floor, and a sound level of 58 dB(A) is measured. MANUFACTURED BY : HB COTES A/S Værkstedsvej 5 DK-4230 Skælskør. Phone +45 58 19 63 22 +45 58 19 58 44 dehum@hbcotes.com...