Non -Direct Vent (Single Pipe ) Piping - Amana xMVC96 series Installation Instructions Manual

Two-stage gas furnace
Table of Contents

Advertisement

T
HE RUBBER ELBOW IS NOT DESIGNED TO SUPPORT A LOAD
RUBBER ELBOW IS MOUNTED EXTERNALLY TO THE FURNACE CABINET
EXTREME CARE MUST BE TAKEN TO ADEQUATELY SUPPORT FIELD
/
,
SUPPLIED VENT
FLUE PIPING
CAUSING BODILY INJURY OR DEATH DUE TO EXPOSURE TO FLUE GASES
INCLUDING CARBON MONOXIDE
A
C
A
LTERNATE
OMBUSTION
(Upflow / Horizontal models only)
When using the alternate venting location, either in a hori-
zontal left side down installation or a vertical installation
using down – venting, an alternate combustion air opening
can be used. A locating dimple is located on the right side of
the furnace cabinet. The locating dimple is 1 7/8" mea-
sured from the front edge of the cabinet in line with the
knock out. To use the alternate combustion air location:
1. Remove screws and combustion air flange from
cabinet.
2. Insert cabinet plug in unused combustion air hole.
3. Drill a pilot hole at the cabinet dimple (size dictated
by knockout tool used).
4. Use a knockout tool to create a 3" diameter hole
5. Install combustion air flange and secure with screws
removed in step one.
B
E SURE NOT TO DAMAGE INTERNAL WIRING OR OTHER COMPONENTS
WHEN REINSTALLING COUPLING AND SCREWS
N
-D
V
(S
ON
IRECT
ENT
INGLE
Non-direct vent installations require only a vent/flue pipe. The
vent pipe can be run horizontally with an exit through the side of
the building or run vertically with an exit through the roof of the
building. The vent can also be run through an existing unused
chimney; however, it must extend a minimum of 12 inches above
the top of the chimney. The space between the vent pipe and the
chimney must be closed with a weather-tight, corrosion-resis-
tant flashing.
Although non-direct vent installations do not require a combus-
tion air intake pipe, a minimum of one 90° elbow should be
attached to the furnace's combustion air intake if: an upright
installation uses the standard intake location, or a horizontal
installation uses the alternate air intake location. This elbow will
guard against inadvertent blockage of the air intake.
V
/F
P
L
ENT
LUE
IPE
ENGTHS AND
NOTE: If either a 90 degree or 45 degree elbow is used for
termination, it must be pointed downward.
Refer to the following table for applicable length, elbows, and
pipe diameter for construction of the vent/flue pipe system of a
non-direct vent installation. In addition to the vent/flue pipe, a
single 90° elbow should be secured to the combustion air intake
WARNING
. W
AS DAMAGE CAN RESULT IN LEAKS
P
IR
ROVISION
CAUTION
.
P
) P
IPE
IPING
D
IAMETERS
to prevent inadvertent blockage. The tee used in the vent/flue
termination must be included when determining the number of
elbows in the piping system.
HEN THE
,
*MVC96/*CVC96 Direct Vent (2 - Pipe) and Non-Direct Vent (1- Pipe)
-
,
Pipe Size
Unit Input
(Btu)
40,000
or 2 1/2
60,000
or 2 1/2
80,000 "B"
2 or 2 1/2
80,000 "B"
80,000 "C"
2 or 2 1/2
80,000 "C"
100,000
2 or 2 1/2
100,000
120,000
2 or 2 1/2
120,000
1)
Maximum allowable limits listed on individual lengths for inlet and flue and
NOT a combination.
2)
Minimum requirement for each vent pipe is five (5) feet in length and one
elbow/tee.
3)
Tee used in the vent/flue termination must be included when determining
the number of elbows in the piping system.
4)
2 1/2" or 3" diameter pipe can be used in place of 2" diameter pipe.
5)
Increased Clearance Configurations using (2) 45 deg. Long Sweep elbows
should be considered equivalent to one 90 deg. elbow.
6)
One 90° elbow should be secured to the combustion air intake connection.
V
/F
P
ENT
LUE
NOTE: If either a 90 degree or 45 degree elbow is used for
termination, it must be pointed downward.
The vent/flue pipe may terminate vertically, as through a roof,
or horizontally, as through an outside wall.
Vertical vent/flue pipe terminations should be as shown in the
following figure. Refer to Vent/Flue Pipe and Combustion Air
Pipe - Termination Locations for details concerning location re-
strictions. The penetration of the vent through the roof must be
sealed tight with proper flashing such as is used with a plastic
plumbing vent.
Horizontal vent/flue pipe terminations should be as shown in the
following figure. Refer to Vent/Flue Pipe and Combustion Air
Pipe. To secure the pipe passing through the wall and prohibit
damage to piping connections, a coupling should be installed on
either side of the wall and solvent cemented to a length of pipe
connecting the two couplings. The length of pipe should be the
wall thickness plus the depth of the socket fittings to be installed
on the inside and outside of the wall. The wall penetration
should be sealed with silicone caulking material.
NOTE: Terminate both pipes in the same pressure zone
(same side of roof, no major obstacles between pipes,
etc.).
14
Maximum Allowable Length of Vent/Flue Pipe
& Combustion Air Pipe (ft)
Number of Elbows
(4)
(in.)
1
2
3
4
2
120
115
110
105
2
95
90
85
80
75
70
65
60
3
200
193
186
179
25
20
15
10
3
200
193
186
179
25
20
15
10
3
200
193
186
179
45
40
35
30
3
95
90
85
80
T
IPE
ERMINATIONS
(6)
(1) (2)
(3) (5)
5
6
7
8
100
95
90
85
75
70
65
60
55
50
45
40
172
165
158
151
5
N/A
N/A
N/A
172
165
158
151
5
N/A
N/A
N/A
172
165
158
151
25
20
15
10
75
70
65
60

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xcvc96 series*cvc96*mvc96

Table of Contents