3. Auto Address Setting

4. Remote Controller Test Run Settings

Request concerning recording the indoor/outdoor unit combination Nos.
After automatic address setting has been completed, be sure to record them for future reference.
List the outdoor unit system address and the addresses of the indoor units in that system in an easily visible location
(next to the nameplate), using a permanent marking pen or similar means that cannot be erased easily.
Example: (Outdoor) 1 – (Indoor) 1-1, 1-2, 1-3...
These numbers are necessary for later maintenance. Please be sure to indicate them.
Checking the indoor unit addresses
Use the remote controller to check the indoor unit address.
<If 1 indoor unit is connected to 1 remote controller>
1. Press and hold the
longer (simple settings mode).
2. The address is displayed for the indoor unit that is connected to
the remote controller.
(Only the address of the indoor unit that is connected to the
remote controller can be checked.)
3. Press the
button again to return to normal remote controller
1
mode.
<If multiple indoor units are connected to 1 remote controller (group control)>
1. Press and hold the
longer (simple settings mode).
2. "ALL" is displayed on the remote controller.
3. Next, press the
4. The address is displayed for 1 of the indoor units which is con-
nected to the remote controller. Check that the fan of that indoor
unit starts and that air is discharged.
5. Press the
indoor unit in sequence.
6. Press the
button again to return to normal remote controller
mode.
4. Remote Controller Test Run Settings
1. Press the remote controller
"TEST" appears on the LCD display while the test run is in progress.
The temperature cannot be adjusted when in Test Run mode.
(This mode places a heavy load on the machines. Therefore use it only when performing the test run.)
2. The test run can be performed using the HEAT, COOL, or FAN operation modes.
The outdoor units will not operate for approximately 3 minutes after the power is turned ON and
NOTE
after operation is stopped.
3. If correct operation is not possible, a code is displayed on the remote controller display.
(Refer to "6. Meaning of Alarm Messages" and correct the problem.)
4. After the test run is completed, press the
troller display.
(To prevent continuous test runs, this remote controller includes a timer function that cancels the test run after
60 minutes.)
* If the test run is performed using the wired remote controller, operation is possible even if the cassette-type ceil-
ing panel has not been installed. ("P09" display does not occur.)
button and
button for 4 seconds or
button and
button for 4 seconds or
button.
button again and check the address of each
button for 4 seconds or longer. Then press the
(Outdoor) 2 – (Indoor) 2-1, 2-2, 2-3...
Indoor unit address
Indoor unit address
Indoor unit address
Indoor unit address
button again. Check that "TEST" disappears from the remote con-
1 - 12
Number changes to indicate
Number changes to indicate
which indoor unit is currently selected.
which indoor unit is currently selected.
Number changes to indicate
Number changes to indicate
which indoor unit is currently selected.
which indoor unit is currently selected.
button.
Test Run

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents