After 10 total minutes, the furnace control board
increases the firing rate to 78% at a rate of 1% per
second.
After 20 total minutes, the furnace control board
increases to 100% at a rate of 1% per second for the
remainder of the call for heat.
The circulator fan is adjusted to the appropriate
CFM, corresponding to the current firing rate.
IGNITION
(80%)
70%
60%
50%
2 MINS.
MIN.
Operation with Conventional 2-Stage Thermostat
(DIP switch selects 2-stage heat)
Call for 1st-Stage Heat - Thermostat contacts close R to W1.
After a successful Light Off Sequence and expiration of the
Ignition Stabilization Period:
The furnace control board adjusts to the low firing
rate.
After 2 minutes, the furnace control board increases
the firing rate to 50% for the next 8 minutes.
Thereafter, the furnace control board will increase
the firing rate 10%, at a rate of 1% per second, every
10 minutes for the remainder of the call for heat
(See above figure).
The circulator fan is adjusted to the appropriate
CFM, corresponding to the current firing rate.
90%
IGNITION
(80%)
70%
60%
50%
2 MINS.
MIN.
Operation with Conventional 2-Stage Thermostat
(DIP switch selects 2-stage heat)
10 MINS.
8 MINS.
Figure 45
10 MINS.
8 MINS.
Figure 46
Call for 2nd-Stage Heat - Thermostat contacts close R to W1
and W2.
After a successful Light Off Sequence and expiration of the
Ignition Stabilization Period:
The furnace control board adjusts to the low firing
rate of 35%.
After 2 minutes, the furnace control board increases
the firing rate to 80%.
Thereafter, the IFC will increase the firing rate by
10%, at a rate of 1% per second, every 10 minutes
for the remainder of the call for heat.
The circulator fan is adjusted to the appropriate
CFM, corresponding to the current firing rate.
100%
IGNITION
(80%)
78%
50%
2 MINS.
MIN.
Call for 2nd-Stage Heat with 1st-Stage call for heat call in
progress, with conventional 2-Stage Thermostat.
The furnace control board increases the firing rate
to 100% at a rate of 1% per second for the remainder
of the W2 call.
The circulator is adjusted to the appropriate CFM,
corresponding to the current firing rate.
Call for 2nd-Stage Heat satisfied; Call for 1st-Stage Heat
remains.
The furnace control board remains at the current
firing rate until the 1st-Stage call for heat is
satisfied.
H
O
EATING
PERATION WITH
)
NICATING
When the Thermostat Heat Setup DIP switch is set
to 2-Stage heat, the furnace control board operation
will be compatible with a CTK01 communicating
thermostat.
When a call for heat is sent, the furnace will go
through the Light Off Sequence, at which time the
Heat Current Demand Status will still show 0%. After
the successful Light Off Sequence and expiration of
the Ignition Stabilization Period:
The furnace control board adjusts to the low firing
rate.
After 2 minutes, the furnace control board accepts
the specific heat requested demand.
UNIT CALL FOR HEAT ENDS
CALL FOR
2ND STAGE HEAT
Figure 47

CTK01 T

(C
HERMOSTAT
-
OMMU
35