Vitorond 200, VD2A Series Service
Calibrate Burner
Check Proper Operation of Door Safety Switch (oil burners only)
(continued)
Inspection and Maintenance
Weishaupt / Riello burners
A Vitorond 200, VD2A boiler with a high-performance
gas burner can achieve a combustion efficiency of up to
85.2%, and up to 87.9% if equipped with a #2 oil burner.
Gas-fired
10% volume CO
, 280° F (138° C) net stack
2
temperature, CO in ppm < 50
Oil-fired
13% volume CO
, 300° F (149° C) net stack
2
temperature, smoke spot 0 - 1 (on the Bacharach Scale)
Refer to the Installation Instructions for Oil
Door Safety Switch
The maximum input published for each boiler size cannot
be exceeded.
Vitorond 200 with Viessmann boiler controls
To further protect the Vitorond 200, VD2A from dew-
point corrosion, the following minimum inputs on a
2-stage burner must be adjusted for the first stage
when the boiler is used in conjunction with a Viessmann
Vitotronic boiler control and when operating with
modulating boiler water temperatures.
Model
Input
Input
Oil
Gas
MBH
MBH
VD2A-125
490
508
VD2A-160
628
650
VD2A-195
765
792
VD2A-230
902
934
VD2A-270
1059
1096
Under partial load conditions, a minimum flue gas
temperature must be met. How high that minimum
flue gas temperature must be depends largely on the
configuration of the chimney insulation, venting material
and venting category (I or III), and height of the chimney.
Refer to the Installation Instructions for
Oil Door Safety Switch
Min. 1-stage
Min. 1-stage
input
input
Oil
Gas
MBH
MBH
294
305
377
390
459
475
541
560
635
658
15