York International DUQ024-060 Installation Manual
York International DUQ024-060 Installation Manual

York International DUQ024-060 Installation Manual

2-5 ton

Advertisement

R-410A
DUQ024-060
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Rigging And Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Roof Curb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Service Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Power And Control Wiring. . . . . . . . . . . . . . . . . . . . . . . . . 10
Compressors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1 Unit Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Unit Accessory Weights . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4 Unit Dimensions Front . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5 Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7 DUQ024-060 Two Stage Gas Heat . . . . . . . . . . . . . . . . 12
8 Natural Gas Pipe Sizing Chart . . . . . . . . . . . . . . . . . . . . 14
9 Propane (LP) Gas Pipe Sizing Chart . . . . . . . . . . . . . . . 14
12 DUQ024-060 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
13 DUQ024-060 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
1 Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Unit 4 Point Load Weight . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4 Dimensions Front and Bottom . . . . . . . . . . . . . . . . . . . . . 8
5 Dimensions Back and Bottom . . . . . . . . . . . . . . . . . . . . . 8
6 Roof Curb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7 Typical Field Control Wiring Diagram For Dual Fuel Heat
Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

General

UP Model DUQ units are dual fuel heat pump units designed for
outdoor installation. Only gas piping, electric power and duct
connections are required at the point of installation.
The two stage gas-fired heaters have spark to pilot ignition. The
tubular heat exchangers are aluminized steel.
The refrigerant system is fully charged with R-410A Refrigerant,
and is tested and factory sealed.

TABLE OF CONTENTS

Gas Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Flue Vent Hood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Bottom Duct Application . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Side Duct Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Blower Speed Selection . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Sequence Of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Adjustment of Temperature Rise. . . . . . . . . . . . . . . . . . . . 30
Checking Gas Heat Input . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Natural Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
LIST OF TABLES
14 Additional Static Resistance . . . . . . . . . . . . . . . . . . . . . . 22
15 Indoor Blower Specifications . . . . . . . . . . . . . . . . . . . . . . 23
16 Delay Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
18 Ignition Control Board Flash Codes . . . . . . . . . . . . . . . . 28
19 Gas Rate Cubic Feet Per Hour . . . . . . . . . . . . . . . . . . . . 31
20 DUQ24 Charging Table . . . . . . . . . . . . . . . . . . . . . . . . . . 34
21 DUQ030 Charging Table . . . . . . . . . . . . . . . . . . . . . . . . 34
22 DUQ036 Charging Table . . . . . . . . . . . . . . . . . . . . . . . . 35
23 DUQ42 Charging Table . . . . . . . . . . . . . . . . . . . . . . . . . . 35
24 DUQ48 Charging Table . . . . . . . . . . . . . . . . . . . . . . . . . . 36
25 DUQ060 Charging Table . . . . . . . . . . . . . . . . . . . . . . . . 36
LIST OF FIGURES
8 Typical Field Power Wiring Diagram . . . . . . . . . . . . . . . 11
10 Flue Vent Outlet Air Hood . . . . . . . . . . . . . . . . . . . . . . . 14
11 Control Board Speed Tap Location . . . . . . . . . . . . . . . . 23
12 Two Stage Gas Valve Front . . . . . . . . . . . . . . . . . . . . . . 30
13 Two Stage Gas Valve Rear . . . . . . . . . . . . . . . . . . . . . . 30
14 Proper Flame Adjustment . . . . . . . . . . . . . . . . . . . . . . . 30
15 R-410A Quick Reference Guide . . . . . . . . . . . . . . . . . . . 37
Safety Considerations
This is a safety alert symbol
labels or in manuals, be alert to the potential for personal injury.
Understand and pay particular attention the signal words
DANGER, WARNING or CAUTION.
DANGER indicates an imminently hazardous situation, which,
if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which,
if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if
not avoided may result in minor or moderate injury. It is also
used to alert against unsafe practices and hazards involving
only property damage.
Management System
. When you see this symbol on
830841-BIM-D-0512
SO 9001
Certified Quality

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DUQ024-060 and is the answer not in the manual?

Questions and answers

Summary of Contents for York International DUQ024-060

  • Page 1: Table Of Contents

    24 DUQ48 Charging Table ......36 12 DUQ024-060 ........16 25 DUQ060 Charging Table .
  • Page 2 Immediately call your gas supplier from a neighbor’s forms: phone. Follow the gas supplier’s instructions. • Technical Guide - DUQ024-060, 832147 d. If you cannot reach your gas supplier, call the fire • General Installation - DUQ024-060, 830841 department.
  • Page 3: Installation

    830841-BIM-D-0512 Approvals Design certified by CSA as follows: For use as a cooling only unit, cooling unit with Improper installation may create a condition where the supplemental electric heat or a forced air furnace. operation of the product could cause personal injury or For outdoor installation only.
  • Page 4: Unit Limitations

    830841-BIM-D-0512 In Canada: If components are to be added to a unit to meet local codes, they are to be installed at the dealer’s and/or customer’s Canadian Electrical Code, CSA C22.1 expense. Installation Codes, CSA - B149.1. Size of unit for proposed installation should be based on heat Local plumbing and waste water codes, and loss/heat gain calculation made according to the methods of Air Other applicable local codes.
  • Page 5: Location

    830841-BIM-D-0512 Location codes. Refer to Table 5 for clearances required for combustible construction, servicing, and proper unit operation. Use the following guidelines to select a suitable location for these units: Unit is designed for outdoor installation only. Condenser coils must have an unlimited supply of air. Do not permit overhanging structures or shrubs to Where a choice of location is possible, position the unit on obstruct condenser air discharge outlet, combustion air...
  • Page 6: Weights And Dimensions

    830841-BIM-D-0512 "D" CENTER OF FRONT GRAVITY UNIT "A" "C" 49-1/8 "B" 47-1/4 Figure 2: Unit 4 Point Load Weight Table 2: Weights and Dimensions Size Weight (lbs.) Center of Gravity 4 Point Load Location (lbs.) 6 Point Load Location (lbs.) Model (Tons) Shipping Operating...
  • Page 7: Unit Dimensions Front

    830841-BIM-D-0512 VENT AIR OUTLET HOOD BLOWER SERVICE ACCESS GAS SUPPLY CONDENSER COIL COMPARTMENT PANEL 1-1/4" DIAMETER HOLE (1/2" NPTF CONNECTION) UNIT CONDENSATE CONNECTION 3/4" NPTF (TRAP RECOMMENDED) 2-3/8 HIGH VOLTAGE CONN. 1-3/8" DIA. 3-3/4 KNOCKOUT REFRIGERANT CONNECTIONS 2-1/2 COMBUSTION AIR GAS SUPPLY INLET LOUVERS 1-1/4"...
  • Page 8: Dimensions Front And Bottom

    830841-BIM-D-0512 19-1/4 11-7/8 HIGH VOLTAGE 8-7/8 CONN. 1-3/32" FRONT DIA. KNOCKOUT GAS SUPPLY 1-5/8" DIA. KNOCKOUT (1/2" NPTF CONNECTION) LOW VOLTAGE CONN. 7/8" DIA. KNOCKOUT 4-5/8 CONDENSATE DRAIN 3/4" NPTF 26-3/4 Figure 4: Dimensions Front and Bottom SIDE SUPPLY 14-1/2 AIR OPENING *CONDENSER 28-3/8...
  • Page 9: Ductwork

    830841-BIM-D-0512 RECOMMENDED DUCT SIZE 17-1/2" x 16-3/4" 42-2/3 45-1/8 40-3/4 17-5/8 17-1/4 43-1/4 OPENING FOR 3-1/2 RETURN AIR DUCT OPENING FOR SUPPLY AIR DUCT RECOMMENDED DUCT SIZE 17-1/8" x 21-1/2" Figure 6: Roof Curb Ductwork Refer to Figures 4 and 5 for information concerning rear and bottom supply and return air duct openings.
  • Page 10: Condensate Drain

    830841-BIM-D-0512 Condensate Drain A condensate trap is recommended to be installed in the condensate drain. The plumbing must conform to local codes. Wear safety glasses and gloves when handling Use a sealing compound on male pipe threads. Install the refrigerants. Failure to follow this warning can cause condensate drain line (3/4”...
  • Page 11: Electrical Data

    830841-BIM-D-0512 Equipment Control Wiring CFMCB YGVI Common Terminal (Programmable Terminal Thermostat Only) Thermostat Figure 7: Typical Field Control Wiring Diagram For Dual Fuel Heat Pump Figure 8: Typical Field Power Wiring Diagram Table 6: Electrical Data OD Fan Supply Max Fuse Compressors Size Motors...
  • Page 12: Duq024-060 Two Stage Gas Heat

    830841-BIM-D-0512 Table 7: DUQ024-060 Two Stage Gas Heat Models Component DUQ024 DUQ030 DUQ036 DUQ042 DUQ048 DUQ060 Nominal Tonnage AHRI COOLING PERFORMANCE Gross Capacity @ AHRI A point (MBH) 23.7 30.1 37.2 43.5 47.7 55.0 AHRI net capacity (MBH) 23.0 30.0 35.6...
  • Page 13: Compressors

    830841-BIM-D-0512 Compressors Gas Heat The scroll compressor used in this product is specifically These single or two stage gas-fired heaters have aluminized- designed to operate with R-410A Refrigerant and cannot be steel tubular heat exchangers with spark to pilot ignition. interchanged.
  • Page 14: Natural Gas Pipe Sizing Chart

    830841-BIM-D-0512 have been completed, open the main shut-off valve Table 8: Natural Gas Pipe Sizing Chart admitting normal gas pressure to the mains. Check all Nominal Inches Iron Pipe Size Length joints for leaks with soap solution or other material suitable In Feet 1/2”...
  • Page 15: Ton

    830841-BIM-D-0512 Table 10: Natural Gas Application Data-Two Stage Input Output Gas Rate Temp. Rise ºF Number of Available On Models (MBH) (MBH) /Hr. At Full Input Burners High Fire/Low Fire High Fire/Low Fire High Fire/Low Fire Min. Max. 2 Ton 70 / 45.5 56 / 36.4 65 / 42...
  • Page 16: Duq024-060

    830841-BIM-D-0512 Airflow Performance Bottom Duct Application Table 12: DUQ024-060 External Static Pressure (Inch Water Gauge) Size Thermostat Speed Model Mode (Tons) Input Watts Watts Watts Watts Watts Watts Watts Watts Watts Y1+O COOL-A Y1+O COOL-B Y1+O COOL-C Y1+O COOL-D Cool...
  • Page 17 830841-BIM-D-0512 Table 12: DUQ024-060 (Continued) External Static Pressure (Inch Water Gauge) Size Thermostat Speed Model Mode (Tons) Input Watts Watts Watts Watts Watts Watts Watts Watts Watts Y1+O COOL-A Y1+O COOL-B Y1+O COOL-C Y1+O COOL-D Cool Y1+Y2+O COOL-A 1100 Y1+Y2+O...
  • Page 18 830841-BIM-D-0512 Table 12: DUQ024-060 (Continued) External Static Pressure (Inch Water Gauge) Size Thermostat Speed Model Mode (Tons) Input Watts Watts Watts Watts Watts Watts Watts Watts Watts Y1+O COOL-A Y1+O COOL-B Y1+O COOL-C 1101 Y1+O COOL-D 1301 Cool Y1+Y2+O COOL-A...
  • Page 19: Duq024-060

    830841-BIM-D-0512 Side Duct Application Table 13: DUQ024-060 External Static Pressure (Inch Water Gauge) Size Thermostat Speed Model Mode (Tons) Input Watts Watts Watts Watts Watts Watts Watts Watts Watts Y1+O COOL-A Y1+O COOL-B Y1+O COOL-C Y1+O COOL-D Cool Y1+Y2+O COOL-A...
  • Page 20 830841-BIM-D-0512 Table 13: DUQ024-060 (Continued) External Static Pressure (Inch Water Gauge) Size Thermostat Speed Model Mode (Tons) Input Watts Watts Watts Watts Watts Watts Watts Watts Watts Y1+O COOL-A Y1+O COOL-B Y1+O COOL-C Y1+O COOL-D Cool Y1+Y2+O COOL-A 1100 Y1+Y2+O...
  • Page 21 830841-BIM-D-0512 Table 13: DUQ024-060 (Continued) External Static Pressure (Inch Water Gauge) Size Thermostat Speed Model Mode (Tons) Input Watts Watts Watts Watts Watts Watts Watts Watts Watts Y1+O COOL-A Y1+O COOL-B Y1+O COOL-C 1101 Y1+O COOL-D 1301 Cool Y1+Y2+O COOL-A...
  • Page 22: Additional Static Resistance

    830841-BIM-D-0512 Table 14: Additional Static Resistance Size Wet Indoor Coil Economizer Filter/Frame Kit Electric Heat (Tons) 0.01 0.00 0.01 0.01 0.00 0.02 0.01 0.00 0.04 0.02 0.01 0.06 (2.0) 0.03 0.01 0.08 1000 0.04 0.01 0.10 1100 0.05 0.01 0.13 1200 0.06 0.02...
  • Page 23: Blower Speed Selection

    830841-BIM-D-0512 Fan Only CFM: Table 15: Indoor Blower Specifications When the connection is made from “R” to “G”, the fan only Size Motor mode is activated. In this mode, the blower will deliver 75% of Eff. Frame (Tons) the cooling system CFM. This connection is factory set from the 1050 (2.0) manufacturer, but can be field adjusted.
  • Page 24 830841-BIM-D-0512 “RVG” terminals on the DCB energizing the reversing valve for When the contactor coil is energized, the compressor operates in first stage mechanical heating. cooling operation. The compressor, reversing valve, outdoor fan motor and blower At the same time the compressor is energized, the “ODF” motor are energized in first stage operation.
  • Page 25 830841-BIM-D-0512 24 Volts AC is sent out of the “W1OUT” terminal of the DCB to Emergency Heat Call the “W1” terminal of the CFMCB and to the “W1” terminal on the When the thermostat is set to emergency heat on the Spark Ignition Control Board (EMCB).
  • Page 26 830841-BIM-D-0512 The EMCB then de-energizes “H-IND” at the DM and provides Defrost Termination – 120 Volts AC out of the “IND” terminal reducing the DM to low Same as when Outdoor Ambient Temperature is above speed. Control voltage is also removed from “HI” at the gas Balance Point as previously discussed.
  • Page 27: Dual Fuel Package Unit Operating Chart

    830841-BIM-D-0512 The unit will continue to operate at full capacity (Gas Heat) until 30 second post purge cycle. At the same time the blower will the thermostat is satisfied. When the thermostat is satisfied, the operate until the on board Blower Off Delay selection of 60, 90, gas heat section is de-energized and the DM will operate for a 120, or 180 seconds expires.
  • Page 28: Ignition Control Board Flash Codes

    830841-BIM-D-0512 will de-energize, but the control will remain in a hard lockout Lockout and not respond to any thermostat demands. While in lockout, the control board keeps the pilot gas valve, The only way to recover from a hard lockout is to remove and main gas valve and induced draft motor de-energized.
  • Page 29: Start-Up

    830841-BIM-D-0512 Safety Controls Set the thermostat to the OFF position. Turn off all electrical power to the unit. The control circuit includes the following safety controls: DO NOT try to light the burners by hand. This appliance is High Pressure Switch (HP)- This switch protects against equipped with an ignition device which automatically lights excessive discharge pressures due to a blocked the burners.
  • Page 30: Adjustment Of Temperature Rise

    830841-BIM-D-0512 Remove the burner assembly from the manifold assembly Hi Fire by moving the burner assembly forward, turn at an angle (2nd Stage) and pull back. Manifold Pressure Low Fire Burners are now accessible for service. (1st Stage) Manifold Pressure Pilot Instruction Adjustment Manual...
  • Page 31: Checking Gas Heat Input

    830841-BIM-D-0512 Table 19: Gas Rate Cubic Feet Per Hour BTUH Output Degrees F Temp Rise = 1.08 x CFM Seconds for Size of Test Dial One Rev. 1/2 cu. ft. 1 cu. ft. BTUH Output CFM = 1.08 x Degrees F Temp Rise Direct Drive Blower All units have direct drive, constant CFM blower motors.
  • Page 32: Typical Wiring Diagrams

    830841-BIM-D-0512 Typical Wiring Diagrams Typical DUQ024 Heat Pump with Two Stage Gas Heat 208/230-1-60 volt Wiring Diagram Johnson Controls Unitary Products...
  • Page 33 830841-BIM-D-0512 Typical DUQ030-060 Heat Pump with Two Stage Gas Heat 208/230-1-60 volt Wiring Diagram Johnson Controls Unitary Products...
  • Page 34: Duq24 Charging Table

    830841-BIM-D-0512 Table 20: DUQ24 Charging Table Air Flow Outdoor Suction Suction Discharge Liquid Delta T Entering Leaving Compressor Indoor Db/Wb Pressure Temp. Pressure Temp. Evap Db Evap Db Amps 300 Cfm/Ton 80/62 300 Cfm/Ton 80/67 300 Cfm/Ton 80/72 300 Cfm/Ton 75/63 400 Cfm/Ton 80/62...
  • Page 35: Duq036 Charging Table

    830841-BIM-D-0512 Table 22: DUQ036 Charging Table Air Flow Outdoor Suction Suction Discharge Liquid Delta T Entering Leaving Compressor Indoor Db/Wb Pressure Temp. Pressure Temp. Evap Db Evap Db Amps 300 Cfm/Ton 10.2 80/62 10.5 300 Cfm/Ton 80/67 10.8 300 Cfm/Ton 10.8 80/72 11.0...
  • Page 36: Duq48 Charging Table

    830841-BIM-D-0512 Table 24: DUQ48 Charging Table Air Flow Outdoor Suction Suction Discharge Liquid Delta T Entering Leaving Compressor Indoor Db/Wb Pressure Temp. Pressure Temp. Evap Db Evap Db Amps 12.3 300 Cfm/Ton 14.7 80/62 16.9 13.2 300 Cfm/Ton 15.0 80/67 15.6 13.5 300 Cfm/Ton...
  • Page 37: 410A Quick Reference Guide

    830841-BIM-D-0512 R-410A QUICK REFERENCE GUIDE Refer to Installation Instructions for specific installation requirements. R-410A efrigerant operates at 50 - 70 percent higher pressures than R-22. Be sure that servicing equipment and replacement components are designed to operate with R-410A. R-410A efrigerant cylinders are rose colored. Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400, or DOT BW400.
  • Page 38 Subject to change without notice. Printed in U.S.A. 830841-BIM-D-0512 Copyright © 2012 by Johnson Controls, Inc. All rights reserved. Supersedes: 830841-BIM-C-0412 York International Corporation 5005 York Drive Norman, OK 73069...