Download Print this page

Hitachi RAS-X18CD Installation Manual

Split-unit air conditioner
Hide thumbs Also See for RAS-X18CD:

Advertisement

FOR SERVICE PERSONNEL ONLY
HITACHI SPLIT-UNIT AIR CONDITIONER
INSTALLATION MANUAL
Indoor Unit
Outdoor Unit
RAS-X18CD
RAC-X18CD

SAFETY PRECAUTION

Read the safety precautions carefully before operating the unit.
The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
!
WARNING ........ Incorrect methods of installation may cause death or serious injury.
!
CAUTION ......... Improper installation may result in serious consequence.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of
operating the unit as described in the user's guide.
This air conditioner uses new refrigerant HFC (R410A)
The basic installation work procedures are the same as conventional refrigerant (R22) models.
However, pay careful attention to the following points:
(1) Since the working pressure is 1.6 times higher than that of conventional refrigerant (R22) models, some of the piping and installation and service tools are special.
Especially, when replacing a conventional refrigerant (R22) model with a new refrigerant R410A model, always replace the conventional piping and fl are nuts with
the R410A piping and fl are nuts.
(2) Models that use refrigerant R410A have a different charging port thread diameter to prevent erroneous charging with conventional refrigerant (R22) and for safety.
Therefore, check beforehand. [The charging port thread diameter for R410A is 1/2 UNF 20 threads per inch.]
(3) Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with refrigerant (R22) models. Also, when storing the piping, securely seal the
openings by pinching, taping, etc.
(4) When charging the refrigerant, take into account the slight change in the composition of the gas and liquid phases, and always charge from the liquid phase
side whose composition is stable.
Please request your sales agent or qualifi ed technician to install your unit. Water leakage, short circuit or fi re may occur if you do the installation work yourself.
Please observe the instructions stated in the installation manual during the process of installation. Improper installation may cause water leakage, electric
shock and fi re.
Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may collapse and impose
danger.
Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing with the electrical work. Use
power cables approved by the authorities of your country.
Be sure to use the specifi ed wire for connecting the indoor and outdoor units. Please ensure that the connections are tight after the conductors of the wire
are inserted into the terminals. Improper insertion and loose contact may cause over-heating and fi re.
Please use the specifi ed components for installation work. Otherwise, the units may collapse or water leakage, electric shock and fi re may occur.
Be sure to use the specifi ed piping set for R410A. Otherwise, this may result in broken copper pipes or faults.
When installing or removing an air conditioner, only specifi ed refrigerant (R410A) shall be allowed, do not allow air or moisture to remain in the refrigeration
cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high that may cause rupture to the refrigeration cycle.
Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fi re, a poisonous gas may occur.
After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the room, coming into
contact with fi re in the fan-driven heater, space heater, etc., a poisonous gas may occur.
Unauthorized modifi cations to the air conditioner may be dangerous. If a breakdown occurs please call a qualifi ed air conditioner technician or electrician.
Improper repairs may result in water leakage, electric shock and fi re, etc.
A circuit breaker or fuse (16A time delay) must be installed. Without a circuit breaker or fuse the danger of electric shock exists.
A main switch with a contact gap of more than 3mm has to be installed in the power supply line to the outdoor unit.
Do not install the unit near a location where there is fl ammable gas. The outdoor unit may catch fi re if fl ammable gas leaks around it.
Please ensure smooth fl ow of water when installing the drain hose.
Piping shall be suitable supported with a maximum spacing of 1m between the supports.
1
Installation of Mounting Plate, Wall Penetration and Installation of Protection Pipe
!
CAUTION
The draining of the water container inside the indoor unit can be done from the
left. Therefore the hanger must be fi xed horizontally or slightly tilted towards the
side of drain hose. Otherwise, condensed water may overfl ow the water container.
Direct Mounting On The Wall
Please use hidden beams in the wall to hold the mounting plate.
Procedures of Installation and Precautions
Procedures to fi x the mounting plate.
1. Drill holes on wall.
2. Push plug into the holes.
(As shown below)
(As shown below)
Procedures to fi x the holder of remote control.
1. Drill holes on wall.
2. Push plug into the holes.
(As shown below)
(As shown below)
Wall Penetration and Installation of Protection Pipe
Drill a ø 65mm hole on
wall which is slightly tilted
towards the outdoor side.
Drill the wall at a small
angle.
Cut the protection pipe
according to the wall
thickness.
Empty gap in the sleeve
of protection pipe should
be completely sealed with
putty to avoid dripping of
rain water into the room.
<
>
IA1137: B
INS RAS-X18CD (EN1) 1
INS RAS-X18CD (EN1) 1
Carefully read through the procedures of proper
installation before starting installation work.
The sales agent should inform customers regarding
the correct operation of installation.
Tools Needed For Installation Work
(
mark is tool exclusive use for R410A)
+
– Screwdriver
Measuring Tape
Pipe Cutter
Hexagonal Wrench Key (
4mm)
Power Drill (ø 65mm ~ ø 80mm)
Pliers or Wrench
Torque Wrench
Adaptor
Flare Tool
Gas Leakage Detector
Manifold Valve
Charge Hose
WARNING
!
CAUTION
!
2
Installation of the Indoor Unit
VERTICALLY DOWNWARD PIPING
Preparation
Connect connecting cord.
Pull out the pipe, connecting cord and drain hose.
Installation
The upper part of the Indoor unit is hanged on the mounting plate.
The projection at the lower part of the Indoor unit is hooked onto the mounting plate.
Push up the (PUSH) sections at the
bottom of the indoor unit and pull the
bottom plate towards you. Then the
claws are released from the stationary
plate.
(The (PUSH) sections are indicated
by 2 arrows in the right fi gure)
3. Fix the mounting plate on wall
with 4.1 x 32 screw
HORIZONTAL PIPING
(As shown in fi gure below)
Preparation
Change of Drain Hose and Installation Procedures.
Exchange the location of drain hose and drain cap during horizontal piping as shown in
fi gure below. Be sure to plug in the drain hose until the insulating material folds upon itself.
Please use pliers to pull out the drain cap.
(This is an easier way to remove the drain cap).
!
WARNING
!
CAUTION
Be sure that the wire is not
HORIZONTAL & DOWNWARD PIPING – MAKING OPENINGS
in contact with any metal
in the wall. Please use
During horizontal or downward piping, use a knife to cut
the protection pipe as wire
openings as shown in fi gure. Then smoothen the edges of
passing through the hollow
part of the wall so as to
openings with a fi le.
prevent the possibility of
damaged by mouse.
Unless it seals completely,
any air with high humidity
flows from outdoor and
any dew may drop.
THE CHOICE OF MOUNTING SITE
WARNING
!
The unit should be mounted at stable, non-vibratory location
which can provide full support to the unit.
CAUTION
!
No nearby heat source and no obstruction near the air outlet is
allowed.
The clearance distances from top, right and left are specifi ed in
fi gure below.
The location must be convenient for water drainage and pipe
Knife
Saw
connection with the Outdoor unit.
To avoid interference from noise please place the unit and its
Vacuum Pump
remote controller at least 1m from the radio, television and inverter
Vacuum Pump
type fl uorescent lamp.
To avoid any error in signal transmission from the remote controller,
please put the controller far away from high-frequency machines
and high-power wireless systems.
The installation height of indoor unit must be 2.3m or more.
Names of Indoor Components
No.
Component's Name
Qty
Mounting Plate
1
1
Screw for Mounting Plate
6
2
( 4 . 1 x 3 2 )
Holder for Remote
Controller
1
3
AAA Size Battery
2
4
Screw for holder of
Remote Controller
2
5
( 3 . 1 x 1 6 )
Remote Controller
6
1
Purifying Filter
2
7
CAUTION
!
Please pull the lower
part of the Indoor unit
outwards to check if the
unit is hooked onto the
mounting plate. Improper
installation may cause
vibration and noise.
HOW TO REMOVE INDOOR UNIT
Condensed water may leak out if not inserted properly.
Turn the piping while holding down the lower
portion of pipe-support by hand.
(Please note the following matters and obtain permission from customer before installation).
!
The outdoor unit must be mounted at a location which can support
heavy weight. Otherwise, noise and vibration will increase.
!
Do not expose the unit under direct sunshine or rain. Besides,
ventilation must be good and clear of obstruction.
The air blown out of the unit should not point directly to animals
or plants.
The clearances of the unit from top, left, right and front are
specifi ed in fi gure below. At least three of the above sides must
be open air.
Be sure that the hot air blown out of the unit and noise do not
disturb the neighbourhood.
Do not install at a location where there is fl ammable gas, steam,
oil and smoke.
The location must be convenient for water drainage.
Place the outdoor unit and its connection wire at least 1m away
from the antenna or signal line of television, radio or telephone.
This is to avoid noise interference.
Do not install outdoor unit facing strong wind direction. It may
damage the fan motor.
Direction of Piping
Figure showing the Installation
of Indoor and Outdoor Unit.
T h e r e a r e 6 d i r e c t i o n s
CAUTION
!
allowed, namely, horizontally
perpendicular to the unit,
This unit is chargeless up to 20m pipe length.
vertically down from right,
horizontally out from right,
h o r i z o n t a l l y o u t t o l e f t ,
horizontally out to right,
vertically down from left.
Be sure to
Don't form the piping downward
completely
at the left of the unit.
seal any
gap with
putty.
Dimension of Mounting Stand
of the Outdoor unit
INSTALLATION OF REFRIGERATING PIPES AFTER CONNECTION
The refrigerating pipes should be adjusted to fit
into the hole on the wall and then ready for further
connection.
The terminals of 2 connected pipes must be covered
with insulator used for terminal connection. Then the
pipes are wrapped with insulation pipe.
Connect the connecting cord after removing electrical
cover. (Refer to "CONNECTION OF POWER CORD")
After adjustment, fi t the connecting cord and pipes
into the space available under the indoor unit. Use
holder to hold them tight.
THE CONNECTION OF REFRIGERATING PIPE DURING THE
INSTALLATION OF INDOOR UNIT
Preparation To Install Refrigerating Pipes
The refrigerating pipes and connecting cord
transform and are attached.
The end of the refrigerating pipes are at locations
marked with "
" symbol.
Installation
Hang the Indoor unit onto the mounting plate. Use the temporary
stand at the back of the Indoor unit to push its lower part
15cm forwards.
Place the drain hose through the hole on the wall.
Wrap the refrigerating pipes with insulation pipe after
connecting refrigerating pipe.
Connect the connecting cord after removing electrical cover.
(Refer to "CONNECTION OF POWER CORD")
After adjustment, the connecting cord and refrigerating pipes
are placed into the space available under the Indoor unit.
The projection of Indoor unit must hook to the mounting
plate.
Pull this to the front
Heat insulation pipe
during the connection
of refrigerating pipes
Connecting cord
to ease task.
Refrigerating pipe
3
Installation of Drain Hose
You are free to choose the side (left or right) for the installation of drain
!
hose. Please ensure the smooth fl ow of condensed water of the Indoor
CAUTION
unit during installation. (Carelessness may result in water leakage.)
WARNING
CAUTION
CAUTION
!
The installation height of indoor
unit must be 2.3m or more.
The indoor piping should be
insulated with the enclosed
insulation pipe. (If the
insulator is insufficient,
please use commercial
products).
The connection of insulated
drain hose.
Please use insulated drain
hose for the indoor piping
(commercial product).
CAUTION
!
The rubber strap used for
fi xing the insulator should
not be tied with great force.
Otherwise, this will damage
heat insulation and causes
water condensation.
CAUTION
!
Please fi x in the plastic core
after fl aring to avoid plastic
chips entering the pipes.
CAUTION
!
Be sure that the
drain hose is not
loosely connected
or bend.
5/8/14 2:05 PM
5/8/14 2:05 PM

Advertisement

loading

Summary of Contents for Hitachi RAS-X18CD

  • Page 1: Safety Precaution

    Turn the piping while holding down the lower any dew may drop. CAUTION unit during installation. (Carelessness may result in water leakage.) portion of pipe-support by hand. < > IA1137: B INS RAS-X18CD (EN1) 1 INS RAS-X18CD (EN1) 1 5/8/14 2:05 PM 5/8/14 2:05 PM...
  • Page 2: Procedures Of Wiring

    CAUTION fi gure beside. Reuse of piping R-22 model only apply if previous model is Hitachi and proper pump down method is used. Take out air conditioner unit. Install New Refrigerant air conditioner To Reuse Old Piping ●...

This manual is also suitable for:

Rac-x18cdRas-dx24cfRac-dx24cf