Additional Specifications For
GE Vertical Zoneline
Heat pump unit shall automatically switch from heat pump
operation to electric resistance heat when it is unable to
provide sufficient heat to maintain room temperature or
when the outdoor temperature falls below 25°F.
Unit shall be equipped with a temperature activated valve
to allow condensate water generated during defrost cycles
to drain into the specified drain system.
Unit shall have a concealed switch to allow heat pump
operation to be overridden and heat provided by electric
resistance heaters regardless of outdoor temperatures.
Heat pump unit shall have Reverse Cycle (hot gas) Defrost
system to maximize heat pump operation and minimize
energy consumption.
To minimize energy consumption, units shall have electric
heaters locked out when outdoor temperatures are above
46°F. Heating will be provided by heat pump operation only.
In the event of a compressor failure during heat pump
operation, the unit shall automatically switch to electric
resistance heat to maintain selected room temperature
regardless of outdoor temperatures.
When the heat mode is selected or when the unit is switched
from off to on in heat mode, the unit shall energize electric
heaters to quickly warm the room to wall thermostat set
point. Heat pump operation will resume on subsequent
heating requirements.
Unit shall have an indoor coil temperature sensor to protect
the compressor when the outdoor temperatures are too high
for heat pump operation.
18
Heat Pumps
®
Additional Specifications Service
Submit complete information with bid covering service
availability, to whom service on units will be assigned,
complete address and phone number, including phone
number of emergency service personnel.
Startup, Adjust, Demonstrate
Contractor shall be responsible for the initial starting of
units, adjustments thereto, cleaning, etc.; to place the units
in required operating condition. Contractor shall demonstrate
to the owner, or his representative, the operation of units for
both summer and winter functions.

Limited Warranty

For one year from date of original purchase, manufacturer
will provide, free of charge, parts and service labor on site to
repair or replace any part of the Zoneline that fails because of
a manufacturing defect.
For an additional four years from the date of original purchase,
manufacturer will provide, free of charge, parts and on-site
service labor to repair or replace any part of the sealed
refrigerating system (compressor, condenser, evaporator, and
all connecting tubing) that fails due to a manufacturing defect.
For the second through fifth year from the date of original
purchase, the manufacturer will provide a limited parts
warranty. The manufacturer will provide, free of charge,
parts that fail as a result of a manufacturing defect. Parts
covered are fan motors, switches, heater, heater protectors,
compressor overload, solenoids, circuit boards, auxiliary
controls, thermistors, frost controls, capacitors, and varistors.
This limited parts warranty does not include labor or
transportation to and from the service shop.
All warranty service is to be provided by manufacturers
factory service centers or by their authorized servicers during
normal working hours.