Utility Closet And Dimensions - GE Zoneline Data Manual

Vertical packaged terminal air conditioners
Hide thumbs Also See for Zoneline:
Table of Contents

Advertisement

UNIT INSTALLED THROUGH FRONT OF CASE
Top View
Architectural Louver
~3"
11-1/2"
10"
10"
duct
3"
min.
4" min.
Unit
front
Door/access panel
• 4" min.from front of case – Unit
installed through FRONT of case.
• 5" min.from front of case – Unit
installed through SIDE of case.
• 3" min.from two sides of case.
Option 1
Access panel with
return air grille
Option 2
Return air grille
A
B
A Minimum recommended access door width: 30"
B Minimum recommended access door height: 50"
16
~1-7/8"
3" min.
Rigid
Inside wall
ductwork
Flexible or
rigid duct
Air discharge
outlet
31"
Secure platform
to the floor
Platform: 23-1/4" x 23-1/4" square
8" min.
for drain
Min. load capacity: 175 lbs.
access
UNIT INSTALLED THROUGH SIDE OF CASE
~3"
3"
min.
Side View
Wall plenum
divider
Filter bracket
Drain fitting 3/4"
Platform
Top View
Architectural Louver
~1-7/8"
11-1/2"
5" min.
10"
duct
10"
Unit front
5" min.
Outside wall
Unit
Wall plenum-extend 1/4" for caulking
Exterior/Outside
Plenum
cutout
32-1/4"H
x 20"W
Drain line
Bottom of case approx. 2"
above bottom of plenum
Bottom of case approx. 2"
above bottom of plenum
Outside wall
Door/access panel
Wall plenum
Field supplied
outer flashing