Appendix B: Technical Specifications
Input
1
Maximum DC power
(Module STC)
Transformer-less,
ungrounded
Maximum input
voltage
Nominal DC input
voltage
Maximum input
current
Maximum back-feed
current
Reverse-polarity
protection
Ground-fault isolation
detection
Overvoltage category
Maximum inverter
efficiency
European weighted
efficiency
Night-time power
consumption
Additional Features
Supported
communication
interfaces
Standards Compliance
Safety
Grid connection
standards
Emissions
WEEE, RoHS
Installation Specifications
AC output
DC input
Maximum installation
height
Dimensions (WxLxH)
Weight
1
For detailed information regarding allowed oversizing, refer to
http://www.solaredge.com/files/pdfs/inverter_dc_oversizing_guide.pdf
SolarEdge Installation Guide – MAN-01-00057-2.2
SE5K
SE7K
SE8K
5500
7700
8800
8.5
12
13.5
97.3
97.3
97.5
RS485, RS232, Ethernet, ZigBee (optional)
VDE-AR-N-4105, VDE 0126-1-1, AS-4777, RD-1663, DK 5940
IEC61000-6-2, IEC61000-6-3, IEC61000-3-11, IEC61000-3-12, FCC part15 class B
SE9K
SE10K
SE12.5K SE15K
9900
11000
13700
Yes
950
750
15
16.5
21
0
Yes
1MΩ Sensitivity
III
98
97.5
97.6
97.7
< 2.5
IEC-62103 (EN50178), IEC-62109
Yes
Cable Gland - diameter 15-21
2 MC4 pairs
2000
540 x 315 x 260
33.2
SE16K
SE17K
16500
17600
18700
22
23
23
97.6
97.7
97.7
Unit
W
Vdc
Vdc
Adc
Adc
%
%
W
mm
m
mm
kg
61