<SP562AT-E, SP802AT-E>
Waterproof rubber cap
• When there is a possibility of freezing of drain at the
cold district or a snowfall area, be careful for drainage
ability of drain. The drainage ability increases when a
knockout hole on the base plate is opened. (Open the
knockout hole to outside using a screwdriver, etc.)
Optional Installation Parts
(Local Procure)
Parts name
Refrigerant piping
A
Liquid side : Ø6.4 mm or Ø9.5 mm
Gas side : Ø12.7 mm or Ø15.9 mm
Pipe insulating material
B
(polyethylene foam, 6 mm thick)
C
Putty, PVC tapes
Refrigerant Piping Connection
CAUTION
TAKE NOTICE THESE IMPORTANT
4 POINTS BELOW FOR PIPING WORK
1. Keep dust and moisture away from inside the
connecting pipes.
2. Tightly connect the connection between pipes
and the unit.
3. Evacuate the air in the connecting pipes using
VACUUM PUMP.
4. Check gas leak at connected points.
<Piping connection>
Capacity
Liquid side
rank
Outer
Thickness
RAV-
diameter
SP56
Ø6.4
SP80
Ø9.5
Knockout hole
Open
Drain nipple
Q'ty
Each one
Each one
Gas side
Outer
Thickness
diameter
0.8
Ø12.7
0.8
Ø15.9
For Reference
If a heating operation would be continuously performed
for a long time under the condition that the outdoor
temperature is 0°C or lower, draining of defrosted water
may be difficult due to freezing of the bottom plate,
resulting in a trouble of the cabinet or fan.
It is recommended to procure an anti-freeze heater
locally for a safety installation of the air conditioner.
For details, contact the dealer.
Knockout of Pipe Cover
<SP562AT-E, SP802AT-E>
Front direction
1
Knockout procedure
• The indoor/outdoor connecting pipes can be con-
nected to 4 directions.
Take off the knockout part of the pipe cover in which
pipes or wires pass through the base plate.
• As shown in the figure, do not remove the pipe cover
from the cabinet so that the knockout hole can be
easily punched. To knock out, it is easily taken off by
hands by punching a position at the lower side of 3
connected parts with screwdriver along the guideline.
• After marking the knockout hole, remove the burr and
mount the attached protective bush and guard
material for pass-through part in order to protect
pipes and wires.
After connecting the pipes, be sure to mount the pipe
cover. The pipe cover is easily mounted by cutting off
the slit at the lower part of the pipe cover.
0.8
1.0
6
Rear direction
Pipe cover
Side direction