Performance; Air Temperature And External Static Pressure Limits - Modine Manufacturing DFP Installation And Service Manual

Gas-fired indoor power vented duct furnaces
Table of Contents

Advertisement

PERFORMANCE

Table 16.1 - Air Temperature Rise - Power Vented Indoor Duct Furnaces ➀ ➁
Model
Btu/Hr
Size
Input
Output
75
75,000
60,000
100,000 80,000
100
125
125,000 100,000
150,000 120,000
150
175,000 140,000
175
200
200,000 160,000
225
225,000 180,000
250
250,000 200,000
300,000 240,000 11111
300
350,000 280,000 11111➄
350
400,000 320,000 11111➄
400
Ratings are shown for elevations up to 2000 feet. For higher elevations, the input rating should be reduced at the rate of 4% per 1000 feet elevation above sea level. For Canada, in
elevations between 2000 and 4500 feet, the unit must be derated to 90% of the rating listed above.
Units approved for use in California by CEC.
Power vented indoor duct furnaces are supplied with a factory installed air baffle. For applications where an air tempature rise less than 60°F is desired, it is recomended to remove
this baffle to reduce system pressure drop.
For Variable Air Movement Applications, see page 13.
The maximum CFM for the 350 and 400 results in a 23°F and a 27°F air temperature rise (respectively) based on the maximum unit pressure drop.

Air Temperature and External Static Pressure Limits

The maximum allowable discharge air temperature is 150°F. The maximum allowable air temperature rise for all Power Vented Units
is 100°F. All duct furnaces are designed for a maximum allowable static pressure of 3.0" W.C. on the heat exchanger.
Figure 16.1 - Recommended Unit Configurations
SINGLE TOP VIEW
2279 CFM
60°F ENTERING
AIR TEMP.
TANDEM TOP VIEW
160,000
2279 CFM
BTU/HR
20°F ENTERING
OUTPUT
AIR TEMP.
65°F
TEMP. RISE
PREHEAT
UNIT
16
20 ➂
40 ➂
50 ➂
60
Max
2778
1389
1111
926
3704
1852
1481
1235
4630
2315
1852
1543
5556
2778
2222
1852
6481
3241
2593
2160
7407
3704
2963
2469
8333
4167
3333
2778
9259
4630
3704
3086
5556
4444
3704
6481
5185
4321
7407
5926
4938
160,000
BTU/HR
125°F DISCHARGE
OUTPUT
AIR TEMP.
65°F
TEMP. RISE
160,000
BTU/HR
150°F DISCHARGE
OUTPUT
AIR TEMP.
65°F
TEMP. RISE
REHEAT
UNIT
Air Temperature Rise Through Unit (°F)
65
70
75
80
CFM
855
794
741
694
1140
1058
988
926
1425
1323
1235
1157
1709
1587
1481
1389
1994
1852
1728
1620
2279
2116
1975
1852
2564
2381
2222
2083
2849
2646
2469
2315
3419
3175
2963
2778
3989
3704
3457
3241
4558
4233
3951
3704
PARALLEL TOP VIEW
OUTPUT 65°F
TEMP. RISE
5698 CFM
20°F ENTERING
AIR TEMP.
OUTPUT 65°F
TEMP. RISE
5-564
85
90
95
654
617
585
871
823
780
1089
1029
975
1307
1235
1170
1525
1440
1365
1743
1646
1559
1961
1852
1754
2179
2058
1949
2614
2469
2339
3050
2881
2729
3486
3292
3119
200,000
BTU/HR
85°F DISCHARGE
SEE SERVICE
CLEARANCES
AIR TEMP.
200,000
BTU/HR
100 ➃
Min
556
741
926
1111
1296
1481
1667
1852
2222
2593
2963

Hide quick links: