Studer Innotec SA
VarioString
User
Level
ref.
Parameter
Combination of the events for the auxiliary contact
Expert
14124
(AUX 2)
Expert
14126 Activated in night mode (AUX 2)
Expert
14127 Delay of activation after entering night mode (AUX 2)
Activation time for the auxiliary relay in night mode
Expert
14128
(AUX 2)
Expert
14130 VarioString is OFF (AUX 2)
Expert
14131 Battery undervoltage (AUX 2)
Expert
14132 Battery overvoltage (AUX 2)
Expert
14133 Earth fault (AUX 2)
Expert
14134 PV error (48h without charge) (AUX 2)
Expert
14135 Overtemperature (AUX 2)
Expert
14136 Bulk charge phase (AUX 2)
Expert
14137 Absorption phase (AUX 2)
Expert
14138 Equalization phase (AUX 2)
Expert
14139 Floating (AUX 2)
Expert
14140 Reduced floating (AUX 2)
Expert
14141 Periodic absorption (AUX 2)
Expert
14143 Battery voltage 1 activate (AUX 2)
Expert
14144 Battery voltage 1 (AUX 2)
Expert
14145 Delay 1 (AUX 2)
Expert
14146 Battery voltage 2 activate (AUX 2)
Expert
14147 Battery voltage 2 (AUX 2)
Expert
14148 Delay 2 (AUX 2)
Expert
14149 Battery voltage 3 activate (AUX 2)
Expert
14150 Battery voltage 3 (AUX 2)
Expert
14151 Delay 3 (AUX 2)
Expert
14152 Battery voltage to deactivate (AUX 2)
Expert
14153 Delay to deactivate (AUX 2)
Expert
14154 Deactivate if battery in floating phase (AUX 2)
Contact activated with the temperature of battery
Expert
14156
(AUX 2)
Expert
14157 Contact activated over (AUX 2)
Expert
14158 Contact deactivated below (AUX 2)
Only activated if the battery is not in bulk phase
Expert
14159
(AUX 2)
Expert
14161 Contact activated with the SOC 1 of battery (AUX 2)
Expert
14162 Contact activated below SOC 1 (AUX 2)
Expert
14163 Delay 1 (AUX 2)
Expert
14164 Contact activated with the SOC 2 of battery (AUX 2)
Expert
14165 Contact activated below SOC 2 (AUX 2)
Expert
14166 Delay 2 (AUX 2)
Expert
14167 Contact activated with the SOC 3 of battery (AUX 2)
Expert
14168 Contact activated below SOC 3 (AUX 2)
Expert
14169 Delay 3 (AUX 2)
Expert
14170 Contact deactivated over SOC (AUX 2)
Expert
14171 Delay to deactivate (AUX 2)
Expert
14172 Deactivate if battery in floating phase (AUX 2)
Expert
14173 Reset all settings (AUX 2)
Expert
14174 Block manual programming (dip-switch)
48
V 1.0
User
Factory value
value
Any (Function
OR)
No
1 min
1 min
No
No
No
No
No
No
No
No
No
No
No
No
No
46.8 Vdc
1 min
No
47.8 Vdc
10 min
No
48.5 Vdc
60 min
54 Vdc
60 min
No
No
3 °C
5 °C
No
No
50 % SOC
12 h
No
30%
0.2 h
No
20%
0 h
90 % SOC
0.2 h
No
-
No
User manual
Need help?