Mitsubishi SUZ-KA35VA Service Manual page 67

Split-type, heat pump air conditioners
Table of Contents

Advertisement

Indication
No. Symptom
LED1 (Red) LED2 (Yellow)
Outdoor unit
20
Once
Lighting
operates.
Twice
Lighting
21
3 times
22
Lighting
4 times
23
Lighting
5 times
Lighting
24
Outdoor unit
operates
9 times
25
Lighting
Lighting
26
Lighting
OC322G
Abnormal point/Condition
Primary current protection
When the input current exceeds 15A.
Secondary current protection
When the current of the compressor exceeds 15A.
High-pressure protection
When the indoor gas pipe temperature exceeds 45
Defrosting in cooling
When the indoor gas pipe temperature falls 3
Discharge temperature
When the discharge temperature exceeds 100
protection
When the frequency of the compressor is kept 80Hz or more and
Low discharge
the discharge temperature is kept under 39
temperature protection
minutes.
Cooling high-pressure
When the outdoor heat exchanger temperature exceeds 58
protection
during operation.
Inverter check mode
When the unit is operated with emergency operation switch.
Normal
Condition
during heating.
or below during cooling.
during operation.
for more than 20
-
67
Correspondence
These symptoms do not mean any abnormality
of the product, but check the following points.
• Check if indoor filters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is
short cycled.
• Check refrigerant circuit and refrigerant amount.
• Refer to 12-5. "Check of LEV".
• Refer to 12-5. "Check of outdoor thermistors".
• Refer to 12-5. "Check of LEV".
• Check refrigerant circuit and refrigerant amount.
This symptom does not mean any abnormality
of the product, but check the following points.
• Check if indoor filters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is
short cycled.
-
-