Carrier Aquazone 50QE900 Installation And Operating Instructions Manual

Water source heat pump commercial programmable thermostat

Advertisement

Quick Links

Installation and Operating Instructions
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Select Thermostat Location . . . . . . . . . . . . . . . . . . . . . . 1
Install Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Set Clock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Heat Pump Configuration . . . . . . . . . . . . . . . . . . . . . . . . 3
Configure Advanced Setup. . . . . . . . . . . . . . . . . . . . . . . 3
Program Thermostat Schedules. . . . . . . . . . . . . . . . . . 4
Calibrate Temperature Sensor. . . . . . . . . . . . . . . . . . . . 6
Light Sensor Adjustment. . . . . . . . . . . . . . . . . . . . . . . . . 6
Check Thermostat Operation. . . . . . . . . . . . . . . . . . . . . 6
Final Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,7
Auto-Changeover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Light-Activated Operation . . . . . . . . . . . . . . . . . . . . . . . . 6
Two-Stage Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Clock Backup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Fan Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Emergency Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Holiday Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Keypad Lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
IMPORTANT: Read entire instructions before starting
the installation.

SAFETY CONSIDERATIONS

Read and follow manufacturer instructions carefully. Fol-
low all local electrical codes during installation. All wiring
must conform to local and national electrical codes. Improper
wiring or installation may damage thermostat.
Recognize safety information. This is the safety alert sym-
bol
. When the safety alert symbol is present on equipment
or in the instruction manual, be alert to the potential for person-
al injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety alert symbol.
DANGER identifies the most serious hazards which will result
in severe personal injury or death. WARNING signifies a haz-
ard which could result in personal injury or death. CAUTION
is used to identify unsafe practices which would result in minor
personal injury or property damage.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111
Book 1
4
Tab
5a
5a
Aquazone™ Water Source Heat Pump
Commercial Programmable Thermostat
Part Numbers 50QE900-220LA
Page
Catalog No. 535-00105
Printed in U.S.A.

GENERAL

The 7-day, commercial, programmable thermostats are
wall-mounted, low-voltage thermostats which maintain room
temperature by controlling the operation of an HVAC (heating,
cooling and ventilation) system. Separate heating and cooling
set points and auto-changeover capability allow occupied and
unoccupied programming for energy savings.
All thermostats allow up to 4 time/temperature settings to
be programmed per 24-hour period. Each thermostat stores
programs for 7 independent days. Batteries are not required.
During power interruption the internal NEVERLOST™ mem-
ory stores programmed schedules for an unlimited time while
the clock continues to run for at least 48 hours.
The thermostat can be configured to accept several different
equipment configurations, and is provided for heat pump
operation.
A light sensor is provided on the thermostat for light activa-
tion. When the sensor detects light (the space is occupied), the
thermostat will enter Occupied 1 mode. If the room is dark, the
thermostat will follow its programmed schedule.

INSTALLATION

Select Thermostat Location -

be mounted:
• approximately 5 ft from the floor
• close to or in a frequently used room, preferably on an
inside partitioning wall
• on a section of wall without pipes or ductwork
• where temperature operating limits are within 41 to
104 F (5 to 40 C)
• where humidity operating range is within 0 to 95% rela-
tive humidity, non-condensing
The thermostat should NOT be mounted:
• close to a window, on an outside wall, or next to a door
leading to the outside
• where exposed to direct light and heat from a lamp, the
sun, a fireplace, or any other temperature-radiating
object which may cause a false reading
• close to or in direct airflow from supply registers or
return air grilles
• in areas with poor air circulation (such as behind a door
or in an alcove)
Form 50QE-4SI
Pg 1
50QE900
The thermostat should
6-03
Replaces: New

Advertisement

Table of Contents
loading

Summary of Contents for Carrier Aquazone 50QE900

  • Page 1: Table Of Contents

    50QE900 Aquazone™ Water Source Heat Pump Commercial Programmable Thermostat Installation and Operating Instructions Part Numbers 50QE900-220LA CONTENTS GENERAL Page The 7-day, commercial, programmable thermostats are wall-mounted, low-voltage thermostats which maintain room SAFETY CONSIDERATIONS ..... . 1 temperature by controlling the operation of an HVAC (heating, GENERAL .
  • Page 2: Install Thermostat

    Install Thermostat 7. Secure mounting base to wall with 2 screws and anchors provided. Ensure all wires exit through hole in mounting base. 8. Adjust wire length and routing to allow proper closure of Before installing thermostat, turn off all power to the unit. the thermostat.
  • Page 3: Set Clock

    Set Clock — The Set Clock button allows the user to change the time and day displayed on the thermostat. Press the Set Clock button. The current time will blink on and off. Press Thermostat the UP ARROW and DOWN ARROW buttons until the cor- rect time is shown.
  • Page 4: Program Thermostat Schedules

    DEADBAND (Step 5) — The deadband is the difference in The schedule is divided into 7 days (Monday through Sunday). temperature above the cooling set point or below the heating Each day has from 2 to 4 time periods (Occupied 1, Occupied set point that the thermostat will wait before turning on the first 2, Occupied 3, Unoccupied) depending on the configuration of stage of heating or cooling.
  • Page 5 Table 3 — Daily Schedule Planner SCHEDULE OF THE Occupied 1 Occupied 2 Occupied 3 Unoccupied WEEK Start / Stop / Heat / Cool Start / Stop / Heat / Cool Start / Stop / Heat / Cool Heat / Cool Monday Tuesday Wednesday...
  • Page 6: Calibrate Temperature Sensor

    NOTE: The thermostat will continue to follow the schedule Check Thermostat Operation — To check thermo- until a new one is entered. stat operation, perform the following procedure: If only one occupied schedule is selected, the Occupied 2 1. Press the Mode button repeatedly until the Heat icon and 3 schedules are skipped.
  • Page 7: Two-Stage Operation

    Two-Stage Operation — DOWN ARROWS to select the number of days that the holi- The second stage of heat or day schedule will be in effect. A value of 0 disables Holiday cool is turned on when the first stage has been on for a mini- mode.
  • Page 8 Copyright 2003 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 PC 111 Catalog No. 535-00105 Printed in U.S.A. Form 50QE-4SI Pg 8 6-03 Replaces: New...