OWNER'S MANUAL P/N 50QE900-511WS A Q U A Z O N E Programmable Digital Thermostat Dual Setpoint 5+1+1 Day Programmable Carrier 3 Occupied, 1 Unoccupied I2:00 Very Easy to Program Large, Easy To Read Display AUTO Thermoglow Backlight No Batteries Required...
Display Mode Indicators Selects the operation mode of the equipment. HEAT - indicates the heat mode. COOL - indicates the air conditioning mode. AUTO - indicates the system will automatically changeover between heat and cool modes as the temperature varies. OFF - indicates the entire system is turned off.
Page 5
Display Override Indication Indicates the current program is currently being overridden for up to 4 hours. Page 7,17. Occupied or Unoccupied Indication Indicates the program number: Occupied 1,2,3, or Unoccupied. Page 8-12. Setup Indication Indicates the thermostat is in the programming mode.
Quick Start Set the Clock and Go Press the Mode button. During Setup & Programming: While holding the Mode, MODE press the Override button Pressing the Mode button for 2 seconds to enter Setup selects different flashing items. OVERRIDE screens. (Represented in dark black) Pressing the Up and Down I2:00...
Basic Operation Select Mode I2:00 The HEAT setting indicates the temperature the room has to reach before the furnace will Press turn on to heat the room. MODE I2:00 The COOL setting indicates the temperature the room has to reach before the air conditioner will turn on to cool the room.
Basic Operation Select Desired Temperature In any mode, adjust the I2:00 desired Set Temperature with AUTO buttons. Pressing the up/down buttons in Auto mode will adjust both the heat and cool set temperatures simultaneously. Pressing the up/down buttons in Heat or Cool modes will adjust only the heat or cool set temperature.
Programming Occupied & Unoccupied Periods Press the Mode button. While holding the Mode, press the Up button for 2 seconds to enter time period programming. MODE Occupied Select the maximum # of occupied periods to be used on any one day. Typically 1.
Page 10
Programming Occupied & Unoccupied Periods unoccupied Adjust the heating set- point for unoccupied periods. (35 - 99) Press MODE MoTuWeThFr Occupied Select the day for Occupied 1. (MoTuWeThFr, Sa, Su) Press MODE 7:00 Start MoTuWeThFr Occupied Adjust the start time for occupied 1.
Page 11
Programming Occupied & Unoccupied Periods Occupied Select the day for Occupied 1. (Sa, Su, MoTuWeThFr) Press MODE 9:00 Start occupied Adjust the start time for occupied 1. Press MODE 5:00 Stop occupied Adjust the stop time for occupied 1. Press MODE occupied 1 Select Occupied 1 to run...
Page 12
Programming Occupied & Unoccupied Periods occupied Select the day for Occupied 1. Press MODE 9:00 Start occupied Adjust the start time for occupied 1. Press MODE 5:00 Stop occupied Adjust the stop time for occupied 1. Press MODE occupied Select Occupied 1 to run on this day (On), or not to run this day (Off).
Page 13
Programming Occupied & Unoccupied Periods PROGRAMMING NOTES If only 1 Occupied period is selected in step 1 on page 8, Occupied 2 & 3 programming steps are skipped. Further, if only 2 occupieds are selected, Occupied 3 programming steps are skipped. Heat &...
Advanced Setup Press the Mode button. MODE While holding the Mode, NOTE: Each step # is located at press the Override button the top right corner of the display for easy reference. for 5 seconds to enter Setup OVERRIDE screens. I2:00 Setup Adjust the time of day...
Page 15
Advanced Setup Setup Adjust the deadband from 1 - 6 degrees. Press MODE Setup Adjust the minimum difference between cooling & heating setpoints. (0 - 6 ) Press MODE Select the cycles per Setup hour limit. d=cycles per hour limit defeated. d1=d + defeat 5 min.
Page 16
Advanced Setup Setup Select thermostat operation in degrees Fahrenheit or Centigrade. Press MODE Setup Select the reversing valve polarity for Heat Pump, O or B. MODE OVERRIDE Press the Mode button. While holding the Mode, press the Override button for 2 seconds to leave the Setup screens.
Advanced Setup Advanced Setup Table Step # Description Range Factory Default Time of day clock set 24 hour 12:00 Am Day of the week Sun - Sat Monday Display Blanking Off / On Fan operation Auto / On Auto Deadband or Temperature swing 1 - 6 Forced minimum difference heat/cool 0 - 6...
About Advanced Features & Operation CLOCK BACKUP - In the event of a power loss, the thermostat internal clock will continue to keep proper time for a minimum of 48 hours without external power or batteries. 2 STAGE OPERATION - The 2nd Stage of heat or cool is turned on when (1) the 1st Stage has been on for a minimum of two minutes, and (2) the temperature spread from the setpoint is equal to or greater than: the setpoint...
Page 19
About Advanced Features & Operation EMERGENCY HEAT - To turn on Emergency Heat press in the Override button. While holding the Override button press the Up button for 2 seconds. The Cool setpoint display will read ‘EH’. I2:00 Press for Emergency Heat OVERRIDE During Emergency Heat the thermostat will turn...
Page 20
About Advanced Features & Operation KEYPAD LOCK - To prevent unauthorized use of the thermostat, the front panel buttons may be disabled. To disable, or ‘lock’ the keypad, press and hold in the Mode button. While holding the Mode button in, press the Up and Down buttons in together.
Page 21
About Advanced Features & Operation DUAL SETPOINT BEHAVIOR - The adjustable setpoint range is: 35 - 99 degrees in Fahrenheit and 7 - 35 degrees in Centigrade. When in the modes Heat or Cool, this adjustable range is unhampered. When adjusting any Auto mode, including programming Occupied and Unoccupied periods, the thermostat will not allow the Heat setpoint to get closer to the Cool setpoint than the value programmed as the minimum difference in...
Page 22
At this point use the Up and Down buttons to calibrate room temperature, if needed. Press the Mode button to return to normal operation. NOTE CAUTION ON PAGE 1. LOCKING COVER w/Tamper Proof Screws Carrier I2:00 I2:00 AUTO AUTO Page 21...
Warranty One- Y ear War r a nt y – ppear s wi t h i n t a l l a t i o n, whet h er or not act u al use begi n s on t h at dat e , t h at he pr o duct does not meet t h i s war r a nt y a new or r e manuf a ct u r e d par t at t h e COMPANY’...