INSTALLATION – SOLAR STORAGE TANK
ASSEMBLY OF SOLAR HOT AND SOLAR COLD PIPE CONNECTIONS
•
Use thread sealing tape or approved thread sealant.
•
All olive compression fittings must use brass or copper olives.
•
Ensure air bleed valve is open when filling collectors.
•
Insulate the air bleed valve and 3 way tee assembly connected to the solar hot pipe with the
150 mm long x 35 mm diam insulation and the solar non return valve at the solar hot (from
collector) inlet of the solar storage tank with the 50 mm long x 35 mm diam insulation. Secure the
insulation with the cable ties supplied.
28