2.4.3 Connect The AC Input

Only one AC input can be connected at a time- damage will
be caused by attempting to simultaneously connect single
phase and three phase inputs.
1. Ensure that the AC supply being connected to the unit is switched off.
2. Ensure the input breakers are switched off.
3. Ensure that Cygnus HPG is in Mode 4: Off.
4. Ensure that the CEE Form connectors are dry; wipe off any excess
moisture with an absorbent cloth.
5. Insert the 230 V AC supply's CEE Form industrial socket into either the
single phase or three phase AC Input plug. See
and Circuit Breakers" on page 16
6. Switch on the AC input's power supply.
7. The LED indicators next to the chosen AC input will illuminate to show
the presence of power.
8. Switch on the unit's input breaker.
"Fig. 5 - Inputs, Outputs