Installation Instructions - McLean Cooling Technology Genesis M13-0116-G1014 Instruction Manual

Mclean genesis air conditioners instruction manual
Table of Contents

Advertisement

INSTALLATION INSTRUCTIONS

1. Inspect air conditioner. Verify functionality before mounting the air conditioner, seeHANDLING AND
TESTING THE AIR CONDITIONER on page 3.
2. Using the cutout dimensions shown in this manual or the cutout template printed on the units
shipping carton, prepare the air "IN" and air "OUT" openings, and mounting bolt hole pattern for the
enclosure.
3. Using the gasket kit provided, install gaskets to air conditioner. See gasket kit illustration in this
manual for proper location.
4. Mount air conditioner on enclosure using mounting bolts and screws provided. "EZ" mount tabs
can be used to hold unit on enclosure while mounting in place. Allow unit to remain upright for a
minimum of five (5) minutes before starting. Caution: Air conditioner must be in upright position
during operation.
5. Refer to top of nameplate for electrical requirements. Connect the power cord to a properly grounded
power supply. Use of an extension cord is not recommended. Electrical circuit should be fused with
slow blow or HACR circuit breaker.
- 4 -
© 2012 Pentair Technical Products
87976469