15.3.

Error Codes Table

Diagnosis
Abnormality / Protection control
display
H00
No abnormality detected
H11
Indoor / outdoor abnormal
communication
H12
Connection capability rank abnormal
H14
Indoor intake air temperature sensor
abnormality
H15
Outdoor compressor temperature
sensor abnormality
H16
Outdoor Current Transformer open
circuit
H19
Indoor fan motor merchanism lock
H23
Indoor heat exchanger temperature
sensor abnormality
H25
E-Ion breakdown
H27
Outdoor air temperature sensor
abnormality
H28
Outdoor heat exchanger temperature
sensor abnormality
H30
Discharge temperature sensor
abnormality
H33
Indoor/Outdoor wrong connection
H38
Indoor/outdoor mismatch (brand code)
H58
Abnormal gas sensor
H97
Outdoor Fan Motor lock abnormality
H98
Indoor high pressure protection
H99
Indoor heat exchanger anti-freezing
protection
F11
Cooling / Heating cycle changeover
abnormality*
F90
System and compressor
microcomputer communication error
F91
Refrigeration cycle abnormal
F93
Outdoor compressor abnormal
revolution
F95
Cooling high pressure protection
F96
IPM (power transistor) overheating
protection
F97
Outdoor compressor overheating
protection
F98
Total running current protection
F99
Outdoor Direct Current (DC) peak
detection
Note:
"O" - Frequency measured and fan speed fixed.
"*" - For cooling only model, it is the indication when indoor heat exchanger sensor or indoor air intake sensor has abnormality.
The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until "beep" sound heard
following by pressing the "CHECK" button at Remote Control.
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors (refer to Error
Codes Table) by using Remote Control or Auto Switch at indoor unit. However, the Remote Control signal receiving sound is
changed from one "beep" to four "beep" sounds.
Abnormality
Judgement
Normal operation
> 1 min after starting
Indoor fan operation
operation
only
Continuous for 90 sec.
after power supplied
Continue for 5 sec.
Continue for 5 sec.
7 times occurance
continuously
Continue for 5 sec.
Continue for 5 sec.
Continue for 5 sec.
Continue for 5 sec.
Continue for 6 hours
4 times occurance
within 30 minutes
2 times occurance
within 5 seconds
2 times occurance
within 20 minutes
4 times occurance
within 20 minutes
4 times occurance
within 20 minutes
4 times occurance
within 20 minutes
3 times occurance
within 20 minutes
7 times occurance
continuously
52
Emergency
Primary location to verify
operation
• Internal / external cable connections
• Indoor / Outdoor PCB
• Intake air temperature sensor
(detective or disconnected)
• Compressor temperature sensor
(detective or disconnected)
• Outdoor PCB
• IPM (Power transistor) module
• Indoor PCB
• Fan motor
O
• Heat exchanger temperature sensor
(Cooling only)
(defective or disconnected)
• Indoor PCB
• E-Ion PCB
O
• Outdoor temperature sensor
(defective or disconnected)
O
• Outdoor heat exchanger
temperature sensor (defective or
disconnected)
• Discharge temperature sensor
• Indoor/Outdoor supply voltage
• Gas sensor
(defective or disconnected)
• Outdoor PCB
• Outdoor Fan Motor
• Air filter dirty
• Air circulation short circuit
• Insufficient refrigerant
• Air filter dirty
• 4-way valve
• V-coil
• Compressor
• Outdoor PCB
• No refrigerant
(3-way valve is closed)
• Outdoor compressor
• Outdoor refrigerant circuit
• Excess refrigerant
• Improper heat radiation
• IPM (Power transistor)
• Insufficient refrigerant
• Compressor
• Excess refrigerant
• Improper heat radiation
• Outdoor PCB
• IPM (Power transistor)
• Compressor