Viessmann Vitodens 200-W Service Instructions Manual page 63

Wall-mounted, gas-fired condensing boiler for operation with natural gas heating input 104 to 352 mbh 30 to 103 kw
Table of Contents

Advertisement

Vitodens 200-W B2HA 80, 100 Service
Heating Circuit 1, 2 and 3
Coding in the factory setting
C5:20
C6:74
D3:14
D4:0
D5:0
D6:0
D7:0
D8:0
E1:1
E2:50
(continued)
Electronic minimum flow
temperature limit 68°F
(20°C)
Electronic maximum flow
temperature limit 165°F
(74°C)
Heating curve slope = 1.4
Heating curve level = 0
The external heating program
changeover changes the
heating program to "Constant
operation with reduced room
temperature" or "Standby
mode"
Heating circuit pump stays in
control mode at signal
"External blocking"
Heating circuit pump stays
in control mode at signal
"External demand"
No heating program changeover
via extension EA1
Do not adjust
With remote control: No display
correction for the actual room
temperature
Possible change
C5:1
Minimum limit adjustable from 1 to
to
260°F (127°C) (limited by boiler-
C5:127
specific parameters).
C6:10
Maximum limit adjustable from 50
to
to 260°F (10 to 127°C) (limited by
C6:127
boiler-specific parameters).
D3:2
Heating curve slope adjustable
to
from 0.2 to 3.5 (see page 35).
D3:35
D4:–13
Heating curve level adjustable from
to
–13 to 40 (see page 35).
D4:40
D5:1
The external heating program
changeover changes to "Constant
operation with standard room
temperature" (subject to coding
address 3A, 3B and 3C).
D6:1
Heating circuit pump stops at signal
"External blocking" (subject to
coding addresses 3A, 3B and 3C).
D6:2
Heating circuit pump starts at signal
"External blocking" (subject to
coding addresses 3A, 3B and 3C).
D7:1
Heating circuit pump stops at signal
"External demand" (subject to
coding addresses 3A, 3B and 3C).
D7:2
Heating circuit pump starts at signal
"External demand" (subject to
coding addresses 3A, 3B and 3C).
D8:1
Heating program changeover
via input DE1 at extension EA1.
D8:2
Heating program changeover
via input DE2 at extension EA1.
D8:3
Heating program changeover
via input DE3 at extension EA1.
--
E2:0
Display correction –5 K
to
to
E2:49
Display correction –0.1 K.
E2:51
Display correction +0.1 K
to
to
E2:99
Display correction +4.9 K.
Coding 2
--
63