Viessmann Vitodens 200-W Service Instructions Manual page 72

Wall-mounted, gas-fired condensing boiler for operation with natural gas heating input 104 to 352 mbh 30 to 103 kw
Table of Contents

Advertisement

Troubleshooting
Fault Codes
Fault code on display
9C
9E
9F
A3
A4
A7
B0
B1
B5
B7
B8
BA
BB
BC
*1
Control mode: Boiler/burner fully operational (fault code must be verified and reset).
Burner in fault mode: Boiler control requires manual reset before burner can resume operation.
Burner blocked: If fault cause is corrected, burner resumes operation.
72
System behavior*1
No solar DHW heating
Control mode
Control mode
Burner blocked
Control mode
Control mode (stays in
factory default setting)
Burner blocked
Control mode (stays in
factory default setting)
Control mode
(factory default setting)
Burner blocked
Burner blocked
Mixing valve regulates to
a flow temperature of
68°F (20°C)
Mixing valve regulates to
a flow temperature of
68°F (20°C)
Control mode without remote
control
Vitodens 200-W B2HA 80, 100 Service
Cause
Tank temperature
sensor % cable broken
No flow rate in collector
circuit or flow rate too
low or temperature
limiter has responded
Solar control module
faulty
Flue gas temperature
sensor not properly
positioned
Max. system pressure
exceeded
Faulty programming
unit
Flue gas temperature
sensor shorted out
Communication fault;
programming unit
(internal)
Internal fault
Boiler coding card
missing, faulty or
incorrect boiler coding
card
Flue gas temperature
sensor cable broken
Communication fault -
accessory kit for
heating circuit 2 with
mixing valve
Communication error,
extension kit for heating
circuit 3 (with mixing
valve)
Communication error,
remote control Vitotrol
heating circuit 1
(without mixing valve)
Corrective action
Check temperature sensor %
on solar control module.
Check solar circuit
pump and solar circuit.
Acknowledge fault message.
Replace solar control module.
Properly install flue gas
temperature sensor.
Check system pressure (max.
system pressure 3 bar).
Check the function and sizing
of the diaphragm expansion
vessel. Vent the heating system
Replace the programming unit.
Check flue gas temperature
sensor (see page 78).
Check connections and
replace programming unit
if required.
Replace the control unit.
Plug in boiler coding card or
replace if faulty.
Check flue gas temperature
sensor (see page 79).
Check extension kit connections
and code.
Check extension kit connections
and code.
Check connections, cable,
coding address "A0" in "Heating
circuit" group and remote
control unit setting.