Mitsubishi Electric CITY MULTI PUHY-400YMF-B Service Handbook page 52

City multi series y, super y
Table of Contents

Advertisement

Classification
Portion
Transmission
Limitation of transmission line length followed? For
1
line
example, 200 m or less (total length: 500 m) at the farthest.
2
1.25 mm
(Remote controller 10 m or less 0.75 mm
3
2-core cable used for transmission line?
4
Transmission line apart from power source line by 5 cm
or more?
5
One refrigerant system per transmission line?
The short circuit connector is changed form CN41 to
6
CN40 on the MAIN board when the system is centralized
control? (Just one outdoor unit. Not all outdoor units.)
No connection trouble in transmission line?
7
System set
Address setting properly done? (Remote controller,
1
indoor unit and outdoor unit.)
Setting of address No. done when shutting off power
2
source?
Address numbers not duplicated?
3
Turned on SW3-8 on indoor unit circuit board when
4
mounting room thermistor sensor?
Before starting
Refrigerant piping ball valve (Liquid pressure pipe, gas
1
pressure pipe) opened?
Turn on power source 12 hours before starting opera-
2
tions?
Check item
2
or more transmission line used?
–49–
Erroneous operation, error stop.
Erroneous operation, error stop.
2
)
Error stop in case multiple-core
cable is used.
Erroneous operation, error stop.
Not operate.
Not operate.
Error stop or not operate.
Error stop or not operate.
Can not be properly set with power
source turned on.
Not operate.
Set temperature not obtained at heating
operations. (Thermostat stop is difficult.)
Error stop.
Error stop, compressor trouble.
Trouble