(11) Liquid Refrigerant Correction Control
The liquid refrigerant correction control adjusts the liquid refrigerant amounts between both accumulators in the
unlikely event that the liquid refrigerant amount in both the constant and variable capacity unit accumulators should
be insufficient, or if and excessive amount of liquid refrigerant is returned from either accumulator.
During this operation, Service LED No. 4 on the variable capacity unit will light up.
Direction of Accumula-
tor Liquid Transfer
Variable Capacity Unit
• In heating mode
Constant Capacity Unit
• Run and stop indoor units
are mixed.
• Pd
Indoor Unit
during an accumulator
overflow preliminary error.
• Td < 110°C
• In heating mode
Variable Capacity Unit
• While the constant capacity
unit is stopped.
Constant Capacity Unit
• During an accumulator
overflow preliminary error
in the variable capacity unit
(AL1 = 2)
• TdSH < 40 deg *1
• In heating mode
Variable Capacity Unit
• During constant capacity
unit operation
Constant Capacity Unit
• When AL1 = 2 is detected in
the variable capacity unit.
• TdSH < 40 deg *1
• In cooling mode
Variable Capacity Unit
• While the constant capacity
unit is stopped.
Constant Capacity Unit
• During an accumulator
overflow preliminary error
in the variable capacity unit
(AL1 = 2)
• Constant capacity unit
AL2 = 0 or 1
• Variable capacity unit
TH6 < 25°C
Variable Capacity Unit
• In heating mode
• Constant capacity unit
switches from operation to
Constant Capacity Unit
stopping.
• Constant capacity unit AL2 = 0
• In heating mode
Constant Capacity Unit
• During an accumulator
overflow error delay in the
Variable Capacity Unit
constant capacity unit
(AL2 = 2)
• Variable capacity unit
AL1 = 0 or 1
Constant Capacity Unit
• During cooling or heating
• During an accumulator
overflow preliminary error
Variable Capacity Unit
in the constant capacity
unit (AL2 = 2)
• Variable capacity unit
AL1 = 0 or 1
* 1 TdSH (Discharge temperature superheating) = Discharge temperature (TH11 or TH12) - Tc (High pressure saturation
Constant Capacity Unit
Start Conditions
Com-
pressor
13k (1.27 MPa), or
OFF
OFF
OFF
OFF
OFF
temperature)
Actuator Action
Variable
capacity
LEV2
SV5b
Other
unit
2000
ON
(open)
2000
ON
(open)
2000
ON
Fan
Opera-
(open)
ON
tion
fre-
quency
level
up
2000
ON
(open)
Opera-
tion
fre-
quency
level
down
2000
ON
LEV1 =
21S4a,
(open)
480
b
SV4 ON
ON
21S4
OFF
–101–
Stopping
LED Monitor
Indoor
Conditions
No.4
Unit
Opera-
While all
• Verify
tion:
indoor units
surplus
nor-
are operat-
refrigerant
mal
ing
• LD1 lights
control
Td
115°C
up
Stop:
LEV = 60
• AL1 = 0 or 1
Liquid
• Continuing
refrigerant
control 2
for 20
minutes
LD3 lights
up
• AL1 = 0 or 1
Liquid
• AL2 = 2
refrigerant
• Continuing
control 4
for 10
LD5 lights
minutes
up
All
• AL1 = 0 or 1
Liquid
indoor
• Continuing
refrigerant
control 6
unit
for 15
LEV = 60
minutes
LD7 lights
up
• AL1 = 0 or 1
Liquid
• Continuing
refrigerant
control 7
for 3 ~ 6
minutes
LD8 lights
up
• AL2 = 0 or 1
Liquid
• AL1 = 2
refrigerant
control 3
• Continuing
for 10
LD4 lights
minutes
up
All
• AL1 = 2
Liquid
indoor
• Continuing
refrigerant
control 5
unit
for 4
LEV = 60
minutes
LD6 lights
up