Mitsubishi Electric SUZ-KA25VA Service Manual page 62

Split-type, heat pump air conditioners
Hide thumbs Also See for SUZ-KA25VA:
Table of Contents

Advertisement

SUZ-KA50VA
SUZ-KA60VA
Outdoor LED indication
Abnormal point
(Failure mode)
LED1
LED2
Outdoor thermistors
Lighting
Once
Twice
3 times
4 times
9 times
5 times
Outdoor control system
6 times
Converter control
system
7 times
5 times
Goes out
6 times
Goes out
SUZ-KA71VA (Except for SUZ-KA50VAR2.TH)
Details of abnormal
Discharge temperature
When a short circuit is detected in the
thermistor
thermistor during operation, or when an
open circuit is detected in the thermistor
after 10 minutes of compressor start-up.
Defrost thermistor
When a short circuit is detected in the
thermistor during operation, or when an
open circuit is detected in the thermistor
after 5 minutes of compressor start-up.
Ambient temperature
When a short or open circuit is detected
thermistor
in the thermistor during operation.
Fin temperature thermistor
P.C. board temperature
thermistor
Outdoor heat exchanger
When a short circuit is detected in the
temperature thermistor
thermistor during operation, or when an
open circuit is detected in the thermistor
after 5 minutes (in cooling) and 10 minutes
(in heating) of compressor start-up.
When nonvolatile memory data cannot
EEPROM
be read properly, unit stops.
Communication error
When the communication between
between P.C. boards
boards protection stop is continuously
performed twice.
Communication between
Communication error occurs between
P.C. boards protection
the electronic control P.C.board and
power board for more than 10 seconds.
Current sensor
Current sensor protection stop is
continuously performed twice.
Current sensor protection
When a short or open circuit is
detected in the current sensor during
compressor operating.
Zero cross detecting circuit
The protection stop of the zero cross
detecting circuit is continuously
performed 10 times.
Zero cross detecting
When zero cross signal cannot be
circuit protection
detected while the compressor is
operating.
Converter protection
When a failure is detected in the
operation of the converter during
operation.
When the bus-bar voltage exceeds
Bus-bar voltage protection (1)
400V or falls to 200V or below during
compressor operating.
Bus-bar voltage protection (2)
When the bus-bar voltage exceeds
Even if this protection
400V or falls to 50V or below during
stop is performed
compressor operating.
continuously 3 times,
it does not mean the
abnormality in outdoor
power system.
Detecting method
62
Check point
• Check the outdoor thermistors.
• Replace the outdoor electronic
control P.C. board.
• Check the outdoor thermistors.
• Replace the outdoor electronic
control P.C. board.
• Check the connecting wire
between outdoor electronic
control P.C. board and power board.
• Replace the power board.
• Check the connecting wire among
electronic control P.C. board,
noise filter P.C. board and power
board.
• Replace the power board.